Communication Modbus
2.5 Modbus Data Format

Data Type - Indications (Read)

2.5.4
The
Indications data type is represented by two bits in holding registers:
[dw_Indications, 1, en_US]
Figure 2-4
Where:
Q: status/quality bit: 0 = OK, 1 = invalid
V: Value bit: 0 = OFF, 1 = ON
Status or Quality Bit Q
If the indication is invalid, the quality bit is set to 1. The value bit can be ignored in this case.
Example: The power frequency is invalid if the voltage is smaller than 15 % of the rated voltage when meas-
uring the frequency. Any limit violation indication based on this value is also invalid.
Value Bit V
The value bit indicates whether an indication is ON (=1) or OFF (=0).

Data Type - Controllable Indications (Read and Write)

2.5.5
The
Controllable Indications data type is needed for:
The binary outputs of the SICAM Q200
Processing internal device commands (for example resetting the energy counters).
The holding register is used for read and write access in this context.
Use as Read Register
[dw_ControllableIndications_Read, 1, en_US]
Figure 2-5
Where:
Q: status/quality bit: 0 = OK, 1 = invalid
V: Value bit: 0 = OFF, 1 = ON
24
Data Type - Indications
Data Type - Controllable Indications - Read Register
SICAM, Multifunctional Recorder, Manual
E50417-C1040-C606-A3, Edition 03.2017