23.4 Step 3. Configuring Modules
The master controller, UPS, and all other modules to be mounted in the FACU back boxes must be configured to operate correctly in the
system via their DIP switch and jumper ports. This section describes the hardware configuration for the master controller and UPS, since
they will always be used in the master controller bay.
23.4.1
Master Motherboard Configuration
The following settings apply to the master motherboard.
P4. City Connect jumpers.
• Local Energy: install jumpers 2, 5, 7, 9, 12, and 13.
• Reverse Polarity: install jumpers 1, 3, 7, 8, and 12.
• Shunt: install jumpers 1, 5, and 13.
• Form C: install jumper 13.
P5-P8, JW1, JW2. (565-274, 565-213 only) Used to enable RS-232/DC Comms or 4120 Network operation.
• If RS-232/DC Comms card is used on the motherboard: install jumpers P5, P6, P7, and P8.
• If a 4120 Network board is used on the motherboard: install jumpers JW1 and JW2.
23.4.2 565-333 Master Controller Configuration
If the 565-333 Master Controller is being used, use the jumper settings described below.
Do not apply power to the system at this time.
• Position 1 – 2: Use port P1.
• Position 2 – 3: Use the service modem.
P3. Controls whether RAM battery backup is enabled.
• Position 1 – 2: Enable RAM battery backup.
• Position 2 – 3: Disable RAM battery backup.
P5. Controls whether Flash EPROM writes are enabled.
• Position 1 – 2: Enable Flash EPROM writes.
• Position 2 – 3: Disable Flash EPROM writes.
P7. Makes the card compatible with a given master display.
• Position 1 – 2: Makes the card compatible with the 565-331 Master Display (5 V LCD). Note that Rev B1 of the 565-331 Master Display
will not work with this setting.
• Position 2 – 3: Makes the card compatible with the 565-173 and 565-331 Rev B1 Master Displays (12 V LCD).
23.4.3 565-148 Master Controller Configuration
If the 565-148 Master Controller is being used, use the jumper settings described below.
P2. Controls whether RAM battery backup is enabled.
• Position 1 – 2: Enable RAM battery backup.
• Position 2 – 3: Disable RAM battery backup.
P3. Controls whether Flash EPROM writes are enabled.
• Position 1 – 2: Enable Flash EPROM writes.
• Position 2 – 3: Disable Flash EPROM writes.
23.4.4 UPS Configuration
Important: Always configure the UPS as described below.
Note: ON = 0; OFF = 1.
DIP Switch SW1. Controls various UPS functions.
page 216
4100ES Fire Alarm System Installation Guide
574-848
Rev. BQ