• When power through auxiliary contacts is not provided by the SPS, use an in-line fuse (208-165). If the power source is not power-
limited to the requirements of UL864, wiring is to be segregated to the non-power-limited spaces of the cabinet.
• The relay circuit is not supervised.
• The relay circuit is rated to switch 2 A at 30 VAC or 30 VDC, resistive load.
• Relay contacts are Form C dry contacts. Suppression is provided to Earth. Do not switch voltages greater than rating, or damage may
result.
22.5.8.2 Wiring
Figure 105 shows SPS auxiliary relay wiring.
22.6 EPS with IDNet 2
This chapter describes how the EPS with an IDNet 2 card is installed and configured by the factory. Check the information in this chapter to
make sure the EPS is installed correctly.
page 181
Figure 105: Auxiliary Relay Wiring
4100ES Fire Alarm System Installation Guide
574-848
Rev. BQ