Card Specifications - Simplex 4100ES Installation Manual

Fire alarm system
Hide thumbs Also See for 4100ES:
Table of Contents

Advertisement

LED1. Illuminates to indicate communication loss with the CPU.
LED2. Illuminates when an RUI ground fault search is active.
LED3. Illuminates when Local Mode is active.
LED4. Illuminates to indicate an RUI Class X primary trouble.
LED5. Illuminates to indicate an RUI Class X secondary trouble.
Note:
• Refer to Figure 34 to see which LEDs are included on which TIC. Most TICs do not contain all LEDs.
• Refer to publication 574-844: Communication and audio interface modules installation instructions, to obtain LED information for
4100-0621, 4100-0622, and 4100-1341 audio riser modules
6.1.9

Card Specifications

Table 7 lists the specifications for all TICs.
Specification
Input Voltage
Output Voltage
Input Current
Specification
Operating Temperature
Humidity
6.2
MINIPLEX System Guidelines
The following rules apply exclusively to MINIPLEX systems. Review each guideline before installing a MINIPLEX 4100ES system.
6.2.1
Guidelines
• All wiring is 18 AWG (minimum) and 12 AWG (maximum).
• All wiring is supervised and power-limited.
• All wiring that leaves the building requires overvoltage protection. Install module inside an UL-Listed electrical box wherever wire
enters or exits the building. A maximum of four 2081-9044 Modules may be connected to one channel. The 2081-9044 is rated for
200 mA (maximum).
• For Class A operation:
- The maximum distance to any device is 2,500 feet (762 m).
- "T" taps are allowed.
- The total maximum cable load (including all "T" taps) is 10,000 feet (3,048 m).
- Maximum allowed line-to-line capacitance ("+" to "-" terminals) is 0.58 uF. For applications with shielded wire, be sure that the total
capacitance from line to line plus the shield to either line is no more than 0.58 uF.
• For Class A or Class X operation, the maximum loop distance is 2,500 feet (762 m). "T" taps are not allowed.
• RUI comms are wired to remote cabinets from the CPU motherboard to one of the following transponder interface cards: 4100-0620
or 4100-0625.
• Annunciators and transponder interface cards support Class X operation when the system is wired Class A.
• The master control panel must be a 4100ES Fire Alarm Control Panel.
• The Class A RUI card supports MINIPLEX transponders and 4602/4603 serial annunciators on the same signaling line circuit.
• Up to 4 RUI cards in the 4100ES Control Panel can be used for distributing transponder wiring in different directions or for supporting
different wiring requirements (such as using a Class X RUI for serial annunciators).
• Up to 31 transponders can be controlled from the 4100ES Control Panel, and can be distributed as required among the RUI cards.
• A maximum of 30 RUI devices between each TIC is supported.
Note: Old legacy, basic, and local mode TICs have been replaced due to component obsolescence. The replacement boards listed below
are functionally equivalent to the legacy boards.
page 67
Table 7: Electrical Specifications
Rating
18-33 VDC
8 V @ 1 A; 100 mV p-p ripple
36 mA for all TICs. 82 mA for a local mode TIC connected to a local mode controller.
Table 8: Environmental Specifications
Rating
32°F to 120°F (0°C to 49°C)
10% to 93% relative humidity at 90°F (32°C)
4100ES Fire Alarm System Installation Guide
574-848
Rev. BQ