7.5.14
Fiber Optic Class X Wiring (565-261, 0566-376, or 746-109 only)
Note:
1.
Refer to general wiring precautions in this chapter, as well as Field Wiring Specifications: document 900-082 for 4100; 900-408
for 4100ES. For specific information about fiber optic wiring, refer to the 900-143 Fiber Tutorial. 2.
2.
The maximum distance between nodes when using the fiber communication path is dependent upon the fiber's multimode
graded index: 10,000 feet (3,048 m) for 50/125 fiber; 15,000 feet (4,572 m) for 62.5/125 fiber. The maximum cable O.D. is 0.118 (3
mm). Reference document 900-143 for other fiber sizes.
3.
ST connectors with long strain relief boots are to be used with the fiber optic cable.
4.
On assembly 565-274, JW1 and JW2 must be installed. Jumper plugs must not be installed on P5-P8.
5.
Cable clamps supplied with 748-531 are used to secure the fiber cable.
page 91
Figure 56: Fiber Optic, Class X Wiring (565-261, 0566-376, or 746-109 only)
4100ES Fire Alarm System Installation Guide
574-848
Rev. BQ