22.1.3

Master Controller Daughter Card LEDs

The master controller daughter card LEDs indicate the card's status. These LEDs are used for troubleshooting.
22.1.4
Master Controller Switches
Switch
Reset (Warm Start)
(0566-719 only)
Reset (Warm Start)
(other than 0566-719 Cards)
CFIG Swap
(0566-719 only)
Cold Start
(0566-719 only)
page 159
Table 28: Master Controller Switches
Description
Short press (< 3 seconds) to activate a software controlled reset (warm start).
Press and hold (> 3 seconds) to force a hardware reset (also a warm start).
Generally unless the CPU card appears to be locked up you should always use the software
controlled reset.
A warm start preserves the logs and the disabled status of any points that are in the disabled
state.
Press (any duration) to cause a warm start. A warm start preserves the logs and the disabled
status of any points that are in the disabled state.
During startup, insert a jumper to revert to the alternate (previous) CFIG. Remove the jumper
after the system reboots and CFIG swap are complete. If you are using an older revision of
the CPU card, press and hold this button. This is used if the current CFIG is corrupt or for
troubleshooting the system.
Note: You will get a "Using previous CFIG" trouble in the system. This trouble will not clear
until a new CFIG is downloaded or you swap back to the original CFIG.
During startup, press and hold this button to clear all history logs and enable any points that
were previously disabled.