4100ES Fire Alarm System Installation Guide
Note: Output of AUX or NAC is 24V nominal. Minimum voltage is 19.5 @ full load and minimum battery; maximum is 31.5V at light load,
high AC line. Aux Loads include 4601-9101 Annunciator, 4100-96xx series Annunciators, 4090 series of IDNet ZAMs and IAMs and any
Listed device operating within the output limits of the AUX. Calculate wiring loss for actual devices used. Compatible Appliances include
4904 series of free-run strobes, 4901 series non-smartsync horns, 4098 series TrueAlarm Sounder Base, 4090-9005 and -9006 SRP and
4009 NAC extenders, used in reverse-polarity activation mode.