13.5.1
Wiring Configurations
RUI cabling can be accomplished either through Class A or Class B wiring.
Class A wiring allows transponder cabinets to communicate with the FACU even in the event of an open circuit somewhere in the loop.
Class A wiring requires that two wires are routed from the CPU motherboard to each RIC, and then back again to the CPU motherboard.
Class B wiring allows "T" tapping, and therefore requires less wiring distance per installation than Class A. Additionally, Class B wiring does
not require end-of-line resistors, because each RIC communicates directly to the CPU.
Important: Make sure these prerequisites are accounted for before wiring:
• All transponder cabinets are installed within 2500 feet (762 m) of the FACU.
• Conductors test free of all grounds.
• All wires are between 12 and 18 AWG, or as the local code dictates.
13.5.2

Class A Wiring

To connect the RUI card to RICs using Class A wiring, read the following instructions and refer to Figure 84, on the next page.
1.
Route wire between 12 and 18 AWG from the + (TB1-8) and - (TB1-6) terminals on the COMMS "A" block of the 562-856/565-217
RUI card to the TB1-8 (+) and TB1-6 (-) terminals on the 565-233 RIC.
2.
Route wire from the first RIC to the next one. Repeat for each transponder cabinet within 2500 feet (762 m).
3.
Route wire from TB1-7 (+) and TB1-5 (-) on the last RIC to + (TB1-4) and - (TB1-2) on the COMMS "B" block of the 562-856/565-217
RUI card.
13.5.3

Class B Wiring

To connect the RUI card to RIC II cards using Class B wiring, read the following instructions and refer to Figure 84, on the next page.
1.
Route wire between 12 and 18 AWG from the + (TB1-8) and - (TB1-6) terminals on the COMMS "A" block of the 562-856/565-217
RUI card to the TB1-8 (+) and TB1-6 (-) terminals on the 565-233 RIC.
2.
Route wire from the first RIC to the next one. Repeat for each transponder cabinet within 2500 feet (762 m).