Simplex 4100ES Installation Manual page 201

Fire alarm system
Hide thumbs Also See for 4100ES:
Table of Contents

Advertisement

Voltage
24V Special Application
rating:
Rating:
2 A, maximum
Wiring gage: 18 AWG (min.)
to 12 AWG (max.)
Wiring Notes:
1. All wiring from the AUX/NAC is power limited.
2. Conductors must test free of all grounds and stray voltages before connection to appliances and panel.
3. Terminate Class B NACs as shown using 733- 894. For Canadian applications, mount end-of-line resistor to Simplex-US Model 431537
EOL plate in accordance with ULC-S527.
4. If circuit is terminated with a 10k EOLR, at the terminals, remove this resistor before wiring.
5. If wiring is routed outside the building, use of a listed secondary protector is required. Use Simplex 2081- 9028 or 2081-9044. A
protector must be installed at each building exit/entrance. Each 2081-9028 adds 0.2 ohms wiring resistance. 2081-9044 adds 6 ohms
wiring resistance, and will greatly reduce wiring distance.
Alarm Current
20 AWG
0.25
617 ft
0.50
308 ft
0.75
206 ft
1.00
154 ft
1.25
123 ft
1.50
103 ft
1.75
88 ft
2.00
77 ft
Note:
This Chart indicates the maximum distance for 1/4 -2A loads. Wiring distance is from the panel terminals to the last appliance. Use of a
2081-9044 protector reduces wiring distance.
page 199
Figure 120: AUX/NAC Terminal
Table 42: AUX/NAC Wiring Specification
Table 43: NAC Wiring Limits
18 AWG
16AWG
981 ft
1560 ft
490 ft
780 ft
327 ft
520 ft
245 ft
390 ft
196 ft
312 ft
163 ft
260 ft
140 ft
223 ft
123 ft
195 ft
4100ES Fire Alarm System Installation Guide
Figure 121: Simple NAC Wiring
14 AWG
12 AWG
2480 ft
3944 ft
1240 ft
1972 ft
827 ft
1315 ft
620 ft
986 ft
496 ft
789 ft
413 ft
657 ft
354 ft
563 ft
310 ft
493 ft
Line Resistance (Ohms)
14.00
7.00
4.67
3.50
2.80
2.33
2.00
1.75
574-848
Rev. BQ