22.6.1
EPS Specifications
22.6.1.1
Card Specifications
Operating
32°F - 120°F (0°C-49°C)
Conditions
Up to 93% relative humidity at 90°F (32°C), non-condensing.
Electrical
AC Input Specifications:
Specifications
Note: Maximum circuit breaker is 20A.
DC Output Specifications: 29 V @ 9 A
Up to 5A normal standby (AUX, "Card Power" and Backplane Power). Any non-alarm current must be subtracted
from 9A alarm current.
DC Input
(battery standby)
Internal Battery
Charges up to 50 Ah (ULC-S527) or 115 Ah (UL-864 Listing) sealed lead-acid batteries connected to the power
Charger
supply.
High Voltage Output: 29 V
Output Current Limit: 3.3 A
IDNAC SLCs
29.5V maximum @ 3A per circuit; 4,000 bits/second
Earth Fault
Earth fault detection is 10k minimum to any circuit.
page 182
Figure 106: EPS Card Layout
Standby – No alarms, SLCs normal: 135 mA / Alarm - 12A @ 24V
With IDNet 2: 235 mA
Per IDNet/IDNAC device: 0.8 mA
4100ES Fire Alarm System Installation Guide
120 V, 50/60 Hz, 4.6 A
220/230/240 V, 50/60 Hz, 2.3 A
574-848