For information on remote expansion bays, refer to
22.4 The System Power Supply (SPS)
This chapter describes how the system power supply (SPS) is installed and configured by the factory. Check the information in this chapter
to make sure the SPS is installed correctly.
22.4.1
SPS Specifications
22.4.1.1
Input/Output/Battery Specifications
Table 30 summarizes the specifications for the SPS.
AC Input Specifications
SPS in Standard U.S./Canada FACU or 4100-5111/5112 SPS 4 A Maximum
SPS in Standard International FACU or 4100-5113 SPS
DC Output Specifications
All SPSs
SPS IDNet Output (see note)
Battery Charger Specifications
Input Voltage Range
page 168
Figure 96: Basic CPU Interconnections
Appendix K: Installing 4100 FACU Components
Table 30: Input and Output Specifications
120 VAC @ 60 Hz, nominal
2 A Maximum
220/230/240 VAC @ 50 or 60 Hz
Minimum: 19.9 VDC (Special Applications)
Maximum: 31.1 VDC
Ripple: 2 VDC p-p @ full load (9 A)
30 V or 35 V @ 1/2A; 36.75V maximum; 3,333 bits per second
21-33 VDC
4100ES Fire Alarm System Installation Guide
(Non-4100ES/4100U).
574-848