- 4190-9050/9051 4-20 mA ZAMs
- 4603-9101 LCD Annunciator
• The total auxiliary current available is 5 A. The total current available for the entire SPS is 9A (special application) or 4A regulated
24VDC, including NAC, auxiliary, and card power.
22.5.7.2 Wiring
The SPS can connect to auxiliary power appliances via the dedicated auxiliary power tap (TB3). If more power is needed, any of the three
NAC outputs can be used for auxiliary power.
Figure Notes:
1.
Maximum allowed NAC current consumption (aux power plus NACs): 9A (Special Application) or 4A regulated 24V dc.
2.
Maximum per NAC: 3 A
3.
Maximum allowed auxiliary power current consumption: 5A (total supply).
4.
Maximum per auxiliary output: 2 A
5.
Class A wiring is possible only if a 4090-9117 Power Isolator is used.
6.
International systems require ferrite beads. Use kit 4100-5129.
22.5.8
SPS Auxiliary Relay Wiring
22.5.8.1 Guidelines
The SPS includes one on-board, programmable relay.
• All wiring must be between 18 AWG and 12 AWG.
• When power through auxiliary contacts provided by the SPS, wiring is power-limited.
page 180
Figure 104: Auxiliary Power Wiring