Simplex 4100ES Installation Manual page 74

Fire alarm system
Hide thumbs Also See for 4100ES:
Table of Contents

Advertisement

6.7.1
Analog Interconnections
Figure 38 is an illustration of Class A and Class B wiring from the analog audio controller to analog audio risers that are in turn connected
to TICs or the Network Audio Riser Controller Module.
Note: Old legacy 0566-218 Analog Audio Controller was replaced due to component obsolescence. The replacement board is the
0566-1011 Analog Audio Controller. It is functionally equivalent to the legacy board.
Note:
1.
Leave the 4.7 K, ½ W resistors (378-056; yellow/violet/red) on the "+" to "-" terminals of unused contacts.
2.
All wiring is 18 AWG to 14 AWG twisted-shielded pair.
3.
Audio wiring is not to be mixed in the same jacket with other wiring (including other audio wiring).
4.
AC voltage rating: 10 VRMS (maximum).
5.
DC voltage rating: 1 VDC (maximum).
6.
Maximum number of analog interface cards per audio riser: 31.
7.
All wiring that leaves the building requires the 2081-9044 Over voltage protector at each entry or exit to the building.
8.
Maximum wire distance: 10,000 feet (3,048 meters).
9.
Wiring must be free of all grounds.
10. Set audio input card jumpers as shown in Aux Audio Input Module Installation Instructions 579-160 .
11. All riser wiring is supervised and power-limited.