650-2013 Fiber Media Card Service Kit MM
62.5um
Qty
Part #
2
156-087
2
650-2077
Note: There are different models for right and left ports. Install the correct model in its respective port on the network card.
7.5.8
Duplex Fiber-Optic Cable Distance Specifications (566-1197, 566-1198, 566-1199, 566-1200)
The available communications distance is determined by the properties of the specific fiber cable used, the overall link topology and the
available power budget.
Fiber type
Multi-mode
50/125 or
62.5/125
numerical
aperture = 0.275
Single-mode
9/125 numerical
aperture = 0.2
Note:
1.
Fiber type: Cable specifications are for:
- 9 micron core with 125 micron cladding, single-mode graded index fiber or
- 50 or 62.5 micron core with 125 micron cladding, multi-mode graded index fiber.
MIFL: Maximum Individual Fiber Loss. Numbers shown are industry standard references. Refer to the specific cable for exact
2.
specifications.
3.
Distance: The maximum distance between nodes is determined by the total loss from the transmitter to the associated receiver
page 87
Table 14: Fiber media card service kits
Description
Wire Clamp
Insulating Sleeve
Figure 52: Duplex fiber wiring
Table 15: Duplex fiber-optic cable communications distance examples
MIFL
Power margin
1.5 dB/km @1300
3 dB
nm
1 dB/km @1310
3 dB
nm
4100ES Fire Alarm System Installation Guide
650-2014 Fiber Media Card Service Kit MM
50um
Qty
Part #
2
156-087
2
650-2077
Distance
5 km
25 km
Description
Wire Clamp
Insulating Sleeve
Budget
Coupler/Slice
Losses
18 dB
0.75 dB max for
each mated pair
0.30 dB max for
for each fusion
splice
22 dB
574-848