Simplex 4100ES Quick Start Manual

Simplex 4100ES Quick Start Manual

Fire control panels
Hide thumbs Also See for 4100ES:

Advertisement

UL, ULC, CSFM Listed; FM Approved;
MEA (NYC) Acceptance*
Features
Master Controller (top) bay:
 32-Bit Master Controller with color-coded operator
interface including raised switches for high confidence
feedback
 Dual configuration program CPU, convenient service port
access, and capacity for up to 2000 addressable points
 CPU assembly includes 2 GB dedicated compact flash
memory for on-site system programming and
information storage
 System power supply (SPS) and charger (9 A total) with
on-board: NACs, IDNet addressable device interface,
programmable auxiliary output and alarm relay
 Available with InfoAlarm Command Center expanded
content user interface (see data sheet S4100-0045)
 Upgrade kits are available for existing control panels
Standard addressable interfaces include:
 IDNet addressable device interface with 250 points that
support TrueAlarm analog sensing and operate with
either shielded or unshielded twisted pair wiring
 Remote annunciator module support via RUI (remote
unit interface) communications port
Optional modules include:
 Building Network Interface Module (BNIC) for Ethernet
connectivity options (see data sheet S4100-0061)
 TrueAlert addressable notification appliance power
supplies with three, 3 A SLC outputs
 Additional IDNet and MAPNET II addressable device
modules and IDNet/MAPNET II quad isolator modules
 IDNet+ output module with built-in quad isolator and
enhanced operation for better retrofit to existing wiring
(see data sheet S4100-0046)
 Fire Alarm Network Interfaces, DACTs, city
connections, and up to five (5) RS-232 ports for printers
and terminals
 IP communicator compatibility
 Alarm relays, auxiliary relays, additional power
supplies, IDC modules, NAC expansion modules
 Service modems, VESDA Air Aspiration Systems
interface, ASHRAE BACnet Interface, TCP/IP Bridges
 LED/switch modules and panel mount printers
 Emergency communications systems (ECS) equipment;
8 channel digital audio or 2 channel analog audio
 Battery brackets for seismic area protection (see page 2)
Compatible with Simplex
 4009 IDNet NAC Extenders, up to ten per IDNet SLC
 TrueAlert Addressable Controllers
4100ES and upgrade kits are UL Listed to:
 UL Std. 864, Fire Detection and Control (UOJZ), and
Smoke Control Service (UUKL)
 UL Std. 2017, Process Management Equipment (QVAX)
 UL Std. 1076, Proprietary Alarm Units-Burglar (APOU)
 UL Std. 1730, Smoke Detector Monitor (UULH)
 ULC Std. S527-99
®
remotely located:
Fire Control Panels
Addressable Fire Detection and Control
Basic Panel Modules and Accessories
Emergency Operating Instructions
A B C
D E F
G H I
1
ZONE
2
SI G
A UX
3
J K L
FB
M N O
IO
P Q R
I DNet
4
5
6
Fire Alarm
ALARMS
Priority 2 Alarm
Supervisory
SYSTEM WARNINGS
Trouble
Ala rm Silenced
AC Power
S T U
P
V W X
A
Y Z /
L
7
8
9
Fire Alarm
Priority 2
Supv
Tr ouble
Alar m
System
'SP ' ( )
, 0 :
Ack
Ack
Ack
Ack
Silence
Reset
N ET
ADDR
DE L
0
Enter
C/Exit
Event
Time
Info
More
Previous
Menu
Enable
On
Arm
Next
Off
Lamp
Disable
Disarm
Auto
Test
Emergency Operating Instructions
Alarm or Warning Condition
How t o Silence Building Signals
System ind icator flashing. Tone On.
Press Alarm Silence.
How to Acknowledge / View Events
How t o Reset System
Press ACK l ocated under fl ashin g indi cator.
Press System Reset.
Local tone wil l silence.
Repeat operation unti l al l events are acknowledged.
Press Ack to si lence tone device.
4100ES Cabinets are Available with
One, Two or Three Bays
Software Feature Summary
CPU provides dual configuration programs:
 Two programs allow for optimal system protection and
commissioning efficiency with one active program and
one reserve
 Downtime is reduced because the system stays running
during download
PC based programmer features:
 Convenient front panel accessed Ethernet port for quick
and easy download of site-specific programming
 Modifications can be uploaded as well as downloaded
for greater service flexibility
 AND, firmware enhancements are made via software
downloads to the on-board flash memory
Introduction
4100ES Series Fire Detection and Control Panels
provide extensive installation, operator, and service features
with point and module capacities suitable for a wide range of
system applications. An on-board Ethernet port provides fast
external system communications to expedite installation and
service activity. Dedicated compact flash memory archiving
provides secure on-site system information storage of
electronic job configuration files to meet NFPA 72 (National
Fire Alarm and Signaling Code) requirements.
Modular design. A wide variety of functional modules
are available to meet specific system requirements.
Selections allow panels to be configured for either
Stand-Alone or Networked fire control operation. InfoAlarm
Command Center options provide convenient expanded
display content (detailed on data sheet S4100-0045).
* See pages 5 and 6 for product that is UL or ULC listed and additional listing information.
This product has been listed by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7165-0026:251(4100ES) and 7300-0026:0368 (4009 TPS) for allowable values and/or
conditions concerning material presented in this document. It is subject to re-examination,
revision, and possible cancellation. Accepted for use – City of New York Department of
Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex
product supplier for the latest status. Listings and approvals under Simplex Time Recorder
Co. are the property of Tyco Fire Protection Products.
ZONE
A B C
D E F
SI G
A UX
G H I
1
2
3
FB
J K L
IO
M N O
P Q R
I DNet
ALARMS
SYSTEM WARNINGS
AC Power
4
5
6
Fire Alarm
Priority 2 Ala rm
Supervisory
Trouble
Alar m Silenced
S T U
V W X
Y Z /
P
A
L
7
8
9
Fire Alarm
Priority 2
Supv
Trouble
Alarm
System
'SP' ( )
, 0 :
Ack
Ack
Ack
Ack
Silence
Reset
NET
0
ADDR
DEL
Event
Mor e
Enter
C/Exit
Time
Info
Previ ous
Menu
On
Enable
Arm
Next
Disable
Off
Auto
Lamp
Disarm
Test
Alarm or Warning Condition
How to Silence Building Signals
System indi cator flashing. Tone On.
Press Alarm Silence.
How to Acknowledge / View Events
How to Reset Syst em
Press ACK located under flashing indicator.
Press System Reset.
Repeat operation until all events are acknowledged.
Press Ack to si lence tone device.
Lo cal to ne will silence.
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
S4100-0031-21 12/2012

Advertisement

Table of Contents
loading

Summary of Contents for Simplex 4100ES

  • Page 1 Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex  ULC Std. S527-99 product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. S4100-0031-21 12/2012...
  • Page 2: Module Bay Description

    “test abnormal” message on display when in test mode  TrueAlarm sensor peak value performance report  “Install Mode” allows grouping of multiple troubles for 4100ES Module Bay Reference uninstalled modules and devices into a single trouble condition (typical with future phased expansion); with...
  • Page 3: Operator Interface Features

    Operator Interface Operator Interface Features  Convenient and extensive operator information is Convenient Status Information. With the locking provided using a logical, menu-driven display door closed, the glass window allows viewing of the display, status LEDs, and available operator switches. ...
  • Page 4 Compatible Peripheral Devices TrueAlarm System Operation The 4100ES is compatible with an extensive list of remote Addressable device communications include operation of peripheral devices including printers, CRT/keyboards (up to TrueAlarm smoke and temperature sensors. Smoke five total), and both conventional and addressable devices sensors transmit an output value based on their smoke including TrueAlarm analog sensors.
  • Page 5 4100U operator interface, or 4100U with or without LCD and operator interface Expansion Bay Upgrade Kit for mounting 4100ES style (4” x 5” modules) in existing 4100 style panels; 4100-2301 Note: When using this kit to upgrade a 4100+ transponder, a 4100-0620 Transponder Interface Card (TIC) is also required for communications to the 4100ES module * For InfoAlarm Command Center expanded content display products, refer to data sheet S4100-0045.
  • Page 6 Model Description 4020 Master Controller Upgrade to 4100ES; Includes New Master Controller with LCD & operator interface assembly, 8 VDC Converter and RUI Interface in a single bay cabinet with locking glass door and retainer; mounts as an adjunct 4100-9833 panel close-nippled to existing 4020 cabinet;...
  • Page 7 ), 2-1/2” L x 1-3/8” W x 1” H (64 mm x 35 mm x 25 mm) * Note: 4100ES English Appliqués are included with 4100ES Upgrade and Retrofit Kits for mounting 4100ES in 4100, 2120, 2001, and Autocall back boxes so that upgrades can be easily identified as 4100ES. 4100ES Appliqué Kits are available for applications such as to update Remote InfoAlarm Displays connected to a panel that was upgraded to 4100ES or for an existing 4100U when the New Master Controller is upgraded to 4100ES and only a software upgrade is required.
  • Page 8: General Specifications

    2 A maximum per NAC; backup) conditions for Auxiliary Power 5 A maximum total Simplex 4901, 4903, 4904, and 4906 Series horns, strobes, and combination horn/strobes and speaker/strobes Special Application (contact your Simplex product representative for compatible appliances) Appliances Regulated 24 DC Power for other UL listed appliances;...
  • Page 9: Expansion Bay Module Loading Reference

    Data Sheet Agent Release Applications S4100-0040 Introducing the 4100ES S4100-0060 4100ES Enclosures S4100-0037 Fire Alarm Network Overview S4100-0055 4100ES Audio and Firefighter Phone Modules S4100-0034 Network Communications S4100-0056 LED/Switch Modules & Printer S4100-0032 Network Display Unit (NDU) S4100-0036 Remote Annunciators...
  • Page 10 TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. Microsoft and Windows are trademarks of Microsoft Corporation. VESDA is a trademark of Xtralis Pty Ltd. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA).