TICs and Audio Riser Modules

Overview
PID List
The Basic TIC
The Local Mode TIC
The following TICs, audio risers, and audio riser controller modules are available for a
4100U/4100ES Fire Alarm Control Panel (FACP) as well as for a 4100U/4100ES MINIPLEX ®
system:
Basic Transponder Interface Card (TIC) Module
Local Mode TIC Module
Analog Audio Riser Module
Digital Audio Riser Module
Network Audio Riser Controller Module
Multiple Command Center Digital Audio Riser Module
Transponder Interface Cards (TICs) receive data from the host panels allowing remote locations
to perform fire alarm functions. TIC modules are optionally available with local mode operation
that provides basic (degraded mode) system functions in the event of a communication loss with
the master panel. TICs receive communications from the host panel using Remote Interface (RUI)
communications with either Style 4 or Style 7 wiring.
For audio systems, audio riser modules are required and are connected directly to TIC modules via
ribbon cable. Audio riser modules support Class A and Class B analog wiring, as well as Style 4
and Style 7 digital audio wiring.
Table 1. TIC, Audio Riser, and Riser Controller PIDS
PID
Description
4100-9600
Basic Transponder
(Expansion Bay with PDI and Basic TIC)
4100-9601
Local Mode Transponder
(Expansion Bay with PDI and Local Mode TIC)
4100-0620
Basic Transponder Interface Card (TIC)
4100-0621
Analog Audio Riser Module
4100-0622
Digital Audio Riser Module
4100-1341
MCC Digital Audio Riser
4100-0623
Network Audio Riser Controller Module
4100-0625
Local Mode TIC
4100-0632
Terminal Block Utility Module
4100-0633
Transponder Cabinet Tamper Switch
The basic TIC is an addressable device that contains an RUI input, audio riser module interface,
and a port for connecting to other transponder modules.
The local mode TIC contains an RUI input, audio riser module interface, port for connecting to
other transponder modules, and terminal block for connecting to an optional Local Mode
Controller. Local Mode Controllers are mounted remotely from the transponder and are available
in red or beige (flush or surface mount). Model numbers are 4601-9108, -9109, -9110, & -9111.
The local mode controller is wired from the local mode TIC, TB2. The outputs for the three
control switches, three LEDs, piezo sounder and power (+24V / 0V) must be connect to the local
mode controller.