SW1-1. Set to 0. Used when the UPS must be retrofitted to for Intelligent Power Supply capabilities.
• Position 0: UPS acts like an Intelligent Power Supply in terms of messages sent to and received from the master controller.
• Position 1: UPS does not use Intelligent Power Supply functionality at all.
SW1-2. Set to 1 unless UPS B-tap is providing power to a 25-Watt Amplifier. Controls how the amplifier uses the backup
battery.
• Position 0: Amplifier switches to battery backup when told to do so by the master controller.
• Position 1: Amplifier switches to battery backup upon loss of AC power.
SW1-3 through SW1-6. These switches work together to configure the UPS for different types of batteries (or no batteries at
all). Refer to Table 48 to determine what settings should be used.
DIP Switch Position
3
4
5
1
0
0
1
0
1
1
1
0
1
1
1
1
0
0
1
1
0
SW1-7. Controls battery charging current.
• Position 0: 50 Ah battery charging.
• Position 1: 110 Ah battery charging.
DIP Switch SW2. Device address DIP switch. See
Use the following jumper settings to continue configuring the UPS.
P6. Battery backup configuration.
• Position 1 – 2: Normal configuration (battery backup).
• Position 2 – 3: No battery backup.
Important: Do not use jumper P6 to bypass troubles from a temporarily disconnected battery.
P7. Amplifier shutdown selection.
• Position 1 – 2: Tap A shutdown enabled.
• Position 3 – 4: Tap B shutdown enabled.
• Position 5 – 6: Tap C shutdown enabled.
P16. Controls Earth Detect configuration.
• Position 1 – 2: Enable Earth Detect.
• Position 2 – 3: Disable Earth Detect.
Note: Jumpers P10, P13, and JW1 through JW7 are not field adjustable.
23.4.5 Configuring Other Cards
Refer to 4100/4100+ Fire Alarm Universal Transponder (UT) Service Instructions (FA4-51-207) to configure other cards that are located in
master controller bays and expansion bays.
page 217
Table 48: UPS SW1 Battery Configurations
UPS Configuration
6
1
Lead-acid battery
0
No battery charger
1
Audio (25 W Amp) and lead-acid battery
0
Audio (25 W Amp) without battery charger
0
NICAD battery
0
Audio (25 W Amp) and NICAD battery
Appendix K: Installing 4100 FACU Components (Non-4100ES/4100U)
4100ES Fire Alarm System Installation Guide
for details.