13.5.4
Wiring Illustration
Figure 84 illustrates Class A and Class B wiring.
Note:
1.
Power wiring is not shown. Connect the RIC II card to the UPS or expansion power supply in the transponder cabinet.
2.
If a UPS is not provided in the transponder cabinet, then 24 VDC must be provided from the host panel.
3.
Maintain correct polarity on terminal connections. Do not loop wires under terminals.
4.
All wiring is supervised and power limited.
page 122
Figure 84: MINIPLEX Wiring