7.5.13
Wired Media Class X Wiring
Note:
1.
Refer to general wiring precautions in this chapter, as well as Field Wiring Specifications: document 900-082 for 4100; 900-408
for 4100ES.
2.
When the 565-413 Interface Card is used with 565-516, -407, –409, or 566-793 Network Card, TB1 on the 565-413 Interface Card
cannot be used. Connection to the motherboard is required as shown.
3.
The shield should only be connected at one end of the line. The shield is connected to the left port.
4.
On assembly 565-274, JW1 and JW2 must be installed. Jumper plugs must not be installed on P5-P8. 5. Each "wired" media cable
requires two ferrite beads, one at each end (included in the shipping group). Refer to installation instructions 574-041 for proper
bead mounting.
5.
Each "wired" media cable requires two ferrite beads, one at each end (included in the shipping group). Refer to installation
instructions 574-041 for proper bead mounting.
page 90
Figure 55: Wired Media, Class X Wiring
4100ES Fire Alarm System Installation Guide
574-848
Rev. BQ