Simplex 4100ES Installation Manual page 94

Fire alarm system
Hide thumbs Also See for 4100ES:
Table of Contents

Advertisement

7.5.15
Wired Media and Fiber Optic Class X Wiring (565-261, 0566-376, or 746-109 only)
Figure 57: Wired Media and Fiber Optic, Class X Wiring (565-261, 0566-376, or 746-109 only)
Note:
1.
Refer to general wiring precautions in this chapter, as well as Field Wiring Specifications: document 900-082 for 4100; 900-408
for 4100ES. For specific information about fiber optic wiring, refer to the 900-143 Fiber Tutorial.
2.
The maximum distance between nodes when using the fiber communication path is dependent upon the fiber's multimode
graded index: 10,000 feet (3,048 m) for 50/125 fiber; 15,000 feet (4,572 m) for 62.5/125 fiber. The maximum cable O.D. is 0.118 (3
mm). Reference document 900-143 for other fiber sizes.
3.
ST connectors with long strain relief boots are to be used with the fiber optic cable.
4.
On assembly 565-274, JW1 and JW2 must be installed. Jumper plugs must not be installed on P5-P8.
5.
Cable clamps supplied with 748-531 are used to secure the fiber cable.
6.
When the 565-413 Interface Card is used with 565-516, -407, –409, or 566-793 Network Card, TB1 on the 565-413 Interface Card
cannot be used. Connection to the motherboard is required as shown.
7.
The shield should only be connected at one end of the line. The shield is connected to the left port.
8.
Each "wired" media cable requires two ferrite beads, one at each end (included in the shipping group). Refer to installation
instructions 574-041 for proper bead mounting.
page 92
4100ES Fire Alarm System Installation Guide
574-848
Rev. BQ