22.3
Interconnecting Bays and Modules
22.3.1
SPS CPU Card Interconnections in the CPU Bay
Use the following directions to connect the CPU to the SPS and other motherboards (refer to Figure 95).
1.
Connect the 734-008 harness from P6 Pwr/Comm connector on the SPS to P10 on the RUI+ CPU motherboard.
Note: If a 734-008 or 734-075 Pwr/Comm harness is connected at P6 on the SPS to provide power to additional modules, you
must relocate it to an available 4-pin Pwr/Comm connector within the FACU.
2.
Make sure connector P3 on the CPU is secured to J1 on the next motherboard to the left. Repeat this for the third (leftmost)
motherboard, if applicable.
page 165
Figure 94: IDNet 2 Card
4100ES Fire Alarm System Installation Guide
574-848
Rev. BQ