Simplex 4100ES Installation Manual page 172

Fire alarm system
Hide thumbs Also See for 4100ES:
Table of Contents

Advertisement

appliances requires use of the associated, Listed, compatible Synchronization Module. Consult supplier of Notification Appliances for
synchronization limits and details.
Simplex Appliances
(Appendix H: IDNAC Compatible Appliances and
Cooper Wheelock Appliances Compatible With 4100ES Wheelock Protocol For Special
system with mix of appliances
Compatible With 4100ES Wheelock Protocol For Special Applications
milliseconds) between power supplies. Appliances listed in
out of visual sync with appliances in
Applications
by about 30 milliseconds. Appliances listed
of audible sync with appliances in
Applications
by a consistent (Wheelock leading by 1/2 second). In order to meet the requirements for visual and audible sync system wide,
all appliances in the system must be exclusively from either
Wheelock Appliances Compatible With 4100ES Wheelock Protocol For Special
Non-pulsing, linear-type Notification Appliances, such as horns or bells may be used up to the full rating (3A / NAC, 9A total for the SPS).
22.4.2 SPS Configuration
This section contains information about SPS jumpers and DIP switches. Refer to
setting the jumpers.
22.4.2.1 Jumper Settings
P1: Earth connect jumper. Note that the P1 location is clearly designated on the PCB silk screen.
• Position 1 – 2: Enables Earth fault monitoring.
• Position 2 – 3: Disables Earth fault monitoring.
Only one power module should be set for earth fault monitoring for each location within a system. Normally, the SPS in the CPU bay is set
to monitor for earth faults. If there is a second SPS connected to the same set of batteries, that SPS should have earth fault monitoring
disabled. Other power modules that can be set to monitor earth fault conditions are TPS, RPS and XBC. When located under common
0V with a TPS, the TPS should be set to monitor earth faults, and other co-located power modules should be set to disable earth fault
monitoring.
P2: If the SPS IDNet outputs are being used, you may change P2 to configure the IDNet shield connection. Note that the P2 pin 1 location is
towards P3.
• Position 1 – 2: Connects the shield to 0 V (default).
• Position 2 – 3: Connects the shield to earth ground.
P3: City Card and Relay Card operation. Note that the P3 pin 1 location is towards P2.
• Position 1-2: Install in position 1-2 only if a relay card 4100-6033 is installed and has relay 3 programmed for operation other than
"Trouble"
• Position 2-3: (default) For City Card operation and for use with 4100-6033 if relay 3 is programmed for "activate on trouble" operation
22.4.2.2 Setting the Device Address
Refer to
Appendix A: The Device Configuration DIP Switch
22.4.3 SPS LED Indications
22.4.3.1 LEDs
The SPS has the following LEDs:
LED1 (yellow). Illuminates when NAC 1 is ON or in Trouble.
LED2 (yellow). Illuminates when NAC 2 is ON or in Trouble.
LED3 (yellow). Illuminates when NAC 3 is ON or in Trouble.
LED4 (yellow). Illuminates to indicate a communications loss with the system CPU; normally off. If this LED is blinking, try re-loading the
software to FLASH.
LED5 (yellow). Indicates IDNet status.
• Slow blink: Class A open circuit trouble.
• Fast blink: Short circuit trouble.
page 170
fromAppendix H: IDNAC Compatible Appliances and
Appendix H: IDNAC Compatible Appliances and Devices
Appendix I: Cooper Wheelock Appliances Compatible With 4100ES Wheelock Protocol For Special
Appendix H: IDNAC Compatible Appliances and Devices
Appendix I: Cooper Wheelock Appliances Compatible With 4100ES Wheelock Protocol For Special
to set the device address for the SPS with DIP switch SW1.
Devices) May not be mixed with Wheelock Appliances
Applications) on a single power supply. A 4100ES
Devicesand
will not meet the UL 864 requirement for Visual synchronization (10
Appendix H: IDNAC Compatible Appliances and Devices
Applications.
4120 Networking
4100ES Fire Alarm System Installation Guide
(Appendix I:
Appendix I: Cooper Wheelock Appliances
will be consistently
will be notably out
or
Appendix I: Cooper
of this document for information on
574-848
Rev. BQ