Simplex 4100ES Installation Manual page 114

Fire alarm system
Hide thumbs Also See for 4100ES:
Table of Contents

Advertisement

11.2.6
Amber Strobes
The 4100ES is compatible with the amber strobes listed below:
• 4906-9205, 4906-9206, 4906-9207 (addressable, visible only, "ALERT" lettering)
• 4906-9107, 4906-9108 (non-addressable, visible only, "ALERT" lettering)
• 4906-9208, 4906-9211 (visible only, with both an amber and a clear lens strobe, respectively marked "ALERT" and "FIRE")
Other models of Simplex brand strobes are available with "ALERT" instead of "FIRE". Refer to the installation instructions for each power
supply for complete lists of compatible appliances.
11.2.7
MNS Wiring
The 4100ES field wiring is "power-limited", with the exception of AC input, battery and the City Circuit option module wiring. For MNS, the
term "power limited" has been replaced by the NEC term "class 2". Wherever this document uses the UL864 term "power limited", it can be
taken to mean class 2. Any wiring deemed "power limited" for UL864 is deemed "class 2" for MNS.
page 112
4100ES Fire Alarm System Installation Guide
574-848
Rev. BQ