5.4
FACU Power Requirements
5.4.1
System Power: ES-PS
The FACU is powered primarily by the ES-PS power supply, which in turn gets its power from the power distribution module (PDM). The AC
branch circuit and the standby battery connect to the PDM. AC and battery power are then distributed to power modules from the PDM
via harness.
In expansion bays, the PDM may connect to the following: ES Series Power Supply or a 100 W Amplifier.
Note: *The 4100-5111, 4100-5112, 4100-5113 SPS is available for expansion bays only.
Important: AC power must be provided to the 4100ES from a dedicated branch circuit.
5.4.2

Power Requirements

ES-PS
page 36
Figure 10: System Power
Table 3: Power requirements
120 V: 3.72 A @ 12.7 A
220-240 V: 1.82 A @ 12.7 A
4100ES Fire Alarm System Installation Guide