Fire alarm system
Hide thumbs Also See for 4100ES:
Table of Contents

Advertisement

2.
Select the RPS located in Transponder 1 (this selects Transponder 1 as the location for the search).
3.
When prompted, select exclusion of AUXPWR circuits.
4.
Start the search. (The panel turns on the earth fault search trouble pseudo-point and the keypad inactivity utility pseudo-point to
disable timeout during the search).
5.
The search completes. The panel indicates FAULT NOT FOUND because the fault is on the excluded AUXPWR circuit. All cards in
Transponder 1 are reset (and the panel turns off the earth fault search trouble pseudo-point).
6.
Repeat the search but include the AUXPWR circuit this time.
7.
The search completes. The panel indicates a fault on the AUXPWR point on the RPS. All cards in Transponder 1 are reset (and the
panel turns off the earth fault search trouble pseudo-point).
8.
Repair the earth fault on AUXPWR.
Even though you have fixed the fault, the trouble from the RPS is still not clearing. Remember that the only two faults you could see at first
were from the SPS and RPS. It is time to find and clear the next fault.
C. Find and repair the next indicated fault on Transponder 1.
1.
Select Location Search.
2.
Select the RPS located in Transponder 1.
3.
When prompted, select exclusion of AUXPWR circuits.
4.
Start the search.
5.
The search completes. The panel indicates a fault on IDNet Channel M2.
6.
Start another search, this time an IDNet Channel Search on Channel M2.
7.
When prompted, select exclusion of AUXPWR circuits.
8.
The search completes. The panel indicates a fault on the IDNet channel between isolators 1 and 2.
9.
Repair the earth fault. The trouble from the RPS is cleared.
page 140
4100ES Fire Alarm System Installation Guide