2 SYSTEM CONFIGURATION

2.6 Forced Stop Input Terminal

Item
Number of input points
Input method
Rated input current
Isolation method
Operating voltage range
ON voltage/current
OFF voltage/current
Input resistance
Response time
External connector type
Applicable wire size
OFF to ON
ON
to OFF
2 - 8
Specifications
Forced stop signal : 1 point
Sink/Source type
3.5mA
Photocoupler
19.2 to 26.4VDC
(+10/ -20%, ripple ratio 5% or less)
17.5VDC or more/3.0mA or more
7VDC or less/1.0mA or less
Approx. 6.8k
4ms or less
2 pin connector
2
0.3mm
(AWG22)
MELSEC-Q