Forced Stop Input Terminal - Mitsubishi Electric Q170MSCPU User Manual

Melsec q series, motion controller
Table of Contents

Advertisement

2 SYSTEM CONFIGURATION

2.5.9 Forced stop input terminal

(1) Table of the forced stop input terminal specifications
Item
Number of input points
Input method
Rated input current
Isolation method
Operating voltage range
ON voltage/current
OFF voltage/current
Input resistance
OFF to ON
Response time
ON to OFF
External connector type
Recommended wire size
Forced stop signal : 1 point
(+10/ -15%, ripple ratio 5% or less)
17.5VDC or more/2.0mA or more
1.8VDC or less/0.18mA or less
0.3 to 1.5mm
2 - 75
Specifications
Sink/Source type
2.4mA
Photocoupler
20.4 to 26.4VDC
Approx. 10k
1ms or less
3 pin connector
2
(AWG16 to AWG22)