NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
With device variants SK 2x0E, a power supply unit is integrated and so no external 24 V DC voltage
supply is required. For sizes 1-3 connection of an external power source (e.g. power supply unit
SK xU4-24V-...) is not provided. No connection terminals are provided for this purpose. Size 4 has
appropriate terminals and allows the connection of an external voltage source ( section 0 "Control
terminal details ").
The SK 2x5E does not have its own analog input. In order to be able to evaluate an analog signal with
this device variant (e.g. from a potentiometer), the analog signal can be converted into a pulse signal
using the power supply unit and made usable by an appropriate digital function of the device.
In
order
to
process
(0(4) - 20 mA) the accessories kit includes a
500 Ω resistor which must be connected between
terminals 12 and 14. The relevant input on the
variable
frequency
parameter P420.
Pos : 169 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
74
current
setpoints
drive
is
adjusted
via
Setpoint
Parameter [array]
0 ... 20 mA
P420 [-02] or [-03]
4 ... 20 mA
P420 [-02] or [-03]
Setting
{26}
{27}