nord NORDAC FLEX SK 200E Series User Manual page 245

Table of Contents

Advertisement

Device model
Rated motor power
(4-pole standard motor)
Line voltage
Input current
Output voltage
3), 4)
Output current
FLA
Min. braking resistance
Motor mounting (fan cooling 5), integrated in device)
Max. continuous power/max. continuous current
Max. permissible ambient temp. with nominal output current
S1
S3 70% ED 10 min
S6 70% ED 10 min (100%/20% Mn)
Wall mounting (fan cooling 5), integrated in device)
Max. continuous power/max. continuous current
Max. permissible ambient temp. with rated output current
S1
S3 70% ED 10 min
S6 70% ED 10 min (100%/20% Mn)
Class
CC, J, R, T, G, L (600 V)
(600 V )
1) Pay attention to derating curve ( section 8.4.4 "Reduced output current due to line voltage").
2) FLA – Full Load Current, maximum current for the entire line voltage range as stated above (380 V – 500 V) according to UL/CSA
3) FLA (S1-40°C)
4) SK 21xE and SK 23xE devices: For use of safe functions (functional safety: STO and SS1) the restrictions regarding the permissible temperature
range according to
BU 0230
must be noted.
5) Fan cooling, temperature-controlled: ON= 55°C, OFF= 50°C,
After-run time when 50°C limit undershot and enable removed: 2 minutes
6) Maximum permissible short-circuit current in the grid
7) "inverse time trip type" in acc. with UL 489
Pos : 731 /Anleitungen/El ektr onik /FU und Starter/8. Z us atzi nform ati onen/!Z us atzi nformati onen (Übersc hrift) [SK 1xxE, SK 2xx E, SK xx xE-FD S] @ 0\mod_1328183966749_14638.docx @ 15181 @ 1 @ 1
BU 0200 en-US-4920
SK 2xxE...
-112-340-
Size
4
400 V
11.0 kW
480 V
15 hp
400 = 0 – 10 V
1)
rms
23.6 A
2)
FLA
20.5 A
400 = 0 – 10 V
1)
rms
23.0 A
2)
20.0 A
motor mounting
2)
FLA
20.0 A
wall mounting
47 Ω
Accessories
S1-40°C 11.0kW/23.0A
40°C
50°C
50°C
S1-40°C 11.0kW/23.0A
45°C
50°C
50°C
slow-blowing
35 A
6)
Isc
[A]
x
60 A
x
60 A
-152-340-
-182-340-
4
4
15.0 kW
18.5 kW
20 hp
25 hp
3 AC 380 V ... 500 V, -20%/+10%, 47 Hz ... 63 Hz
32.0 A
40.5 A
28.0 A
35.5 A
3 AC 0 ... line voltage
32.0 A
40.0 A
28.0 A
35.0 A
28.0 A
35.0 A
33 Ω
27 Ω
4)
15.0kW/32.0A
18.5kW/40.0A
40°C
40°C
49°C
41°C
49°C
41°C
4)
15.0kW/32.0A
18.5kW/40.0A
45°C
41°C
50°C
43°C
50°C
43°C
General fuses (AC) (recommended)
50 A
50 A
UL-approved fuses (AC)
60 A
60 A
60 A
60 A
7 Technical Data
-222-340-
4
22.0 kW
30 hp
46.5 A
42.5 A
46.0 A
42.0 A
42.0 A
24 Ω
22.0kW/46.0A
40°C
41°C
41°C
22.0kW/46.0A
40°C
42°C
41°C
63 A
60 A
60 A
245