NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Value
Function
67
Dig. Out man/auto set
"Set
digital
manually/automatically"
68
Dig.out manual set
"Set digital output manually"
69
Speed meas. with ini.
"Speed measurement with initiator"
70
Evacuation mode
"Activate evacuation run"
3
71
Motorpot. F+ and Save
"Motor potentiometer function
Frequency + with automatic saving"
3
72
Motorpot. F- and Save
"Motor potentiometer function
Frequency - with automatic saving"
2
73
Inhibit right + quick
"Disable clockwise rotation + fast
stop"
2
74
Inhibit left + quick
"Disable counterclockwise rotation +
fast stop"
75
DO 2 man/auto set
"Set
digital
manually/automatically"
76
DO 2 man. set
"Set digital output 2 manually"
77
... 78 reserved for POSICON
79
Rotorpos. Ident
80
PLC stop
1
If no digital input has been parameterized to "Enable right" or "Enable left" and with devices from SK 22xE, all AS-i relevant
BUS-In bits (P480) are deactivated and DIP switches S1 "3- 5" are in the factory setting, the actuation of a fixed frequency or
the jog frequency leads to the enabling of the variable frequency drive. The rotation field direction depends on the sign of the
setpoint.
2
Also effective for BUS control (e.g. RS232, RS485, CANopen, AS-Interface, ...)
178
Description
Set digital output 1 manually, or via the function set in (P434)
output
Set digital output 1 manually
Simple speed measurement (impulse measurement) with initiator
This also provides the possibility of operation with a very low DC
link voltage (e.g. using batteries). With this function the charging
relay is activated and existing monitoring functions are
deactivated.
CAUTION! There is no overload monitoring! (e.g. lifting gear)
With this "motor potentiometer function" a setpoint (sum) is set
via the digital inputs, and simultaneously stored. With control
enabling R/L this is then started up in the correspondingly
enabled direction. On change of direction the frequency is
retained.
Simultaneous activation of the +/- function causes the frequency
setpoint value to be set to zero.
The frequency setpoint can also be displayed or set in the
operating value display (P001 = 30, "Cur. set value MP-S") or in
P718.
Any minimum frequency set (P104) is still effective. Other
setpoint values, e.g. analog or fixed frequencies, can be added or
subtracted.
The adjustment of the frequency setpoint value is performed with
the ramps from P102/103.
Same as setting 31 but coupled to the "quick stop" function.
Same as setting 32 but coupled to the "quick stop" function.
output
2
Same as function 67 but for digital output 2 (only SK 2x0E)
Same as function 68 but for digital output 2 (only SK 2x0E)
BU0210
Exact knowledge of the rotor position is essential for PMSM
operation. Rotor position identification is performed if the
following conditions are met:
The variable frequency drive is in the status "ready to switch-
on",
The rotor position is not known (see P434, P481, function
"28"),
Function "2" is selected in P336.
The program execution of the integrated PLC is stopped for as
long as the signal is present.
Signal
High
High
Pulses
High
High
High
Low
Low
High
High
10
flank
High
BU 0200 en-US-4920