Bus status via PLC
P353
(Bus status via PLC)
0 ... 3
This parameter can be used to determine how the control word (CTW) for the master function and
the status word (STW) of the variable frequency drive undergo further processing by the PLC.
{ 0 }
0 = Off: The control word (CTW) of the master function (P503≠0) and the status word (STW)
1 = CTW for broadcast: The control word (CTW) for the master value function (P503≠ 0) is set
2 = STW for bus: The status word (STW) of the variable frequency drive is set by the PLC. In
3 = CTW Broadcast&STWBus: See setting 1 and 2
Pos : 419 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P355 – PLC Integer Sollwert @ 9\m od_1448364290270_14638.docx @ 266516 @ @ 1
P355
[-01]
PLC integer setvalue
...
(PLC integer setpoint)
[-10]
0x0000 ... 0xFFFF
Data can be exchanged with the PLC via this INT array. This data can be used by the appropriate
process variables in the PLC.
all = { 0 }
Pos : 420 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P356 – PLC Long Sollw ert @ 9\mod_1448376305117_14638.doc x @ 266622 @ @ 1
P356
[-01]
PLC long setvalue
...
(PLC long setpoint)
[-05]
0x0000 0000 ...
Data can be exchanged with the PLC via this DINT array. This data can be used by the
appropriate process variables in the PLC.
0xFFFF FFFF
all = { 0 }
Pos : 421 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P360 – PLC Anzeigew ert @ 9\m od_1448376691352_14638.docx @ 266655 @ @ 1
P360
[-01]
PLC display value
...
(PLC display value)
[-05]
-2 000 000,000 ...
The parameter is only used to display the PLC date. This parameter can be written by the PLC
via the corresponding process variables. The values are not saved!
2 000 000.000
all = { 0.000 }
Pos : 422 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P370 – PLC Status @ 9\mod_1448364654868_14638.docx @ 266549 @ @ 1
PLC status
P370
(PLC status)
0 ... 63
Displays the actual status of the PLC.
dec
Bit 0 = P350=1: Parameter P350 was set in the "Activate internal PLC" function
Parameter Box:
Bit 1 = PLC active: The internal PLC is active.
0x00 ... 0x3F
Bit 2 = Stop active: The PLC program is in "Stop" status.
Simple Box/Control Box:
Bit 3 = Debug active: Error checking of the PLC program is running.
0x00 ... 0x3F
Bit 4 = PLC fault: The PLC has an error but PLC user errors 23.xx are not displayed here.
Bit 5 = PLC stopped: The PLC program was stopped (single step or breakpoint).
all = { 0 }
Pos : 423 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
BU 0200 en-US-4920
undergo further processing by the PLC without change.
by the PLC. In order to do this, the control word must be redefined accordingly in the PLC
using process value "34_PLC_Busmaster_Control_word".
order to do this, the status word must be redefined accordingly in the PLC using process
value "28_PLC_status_word".
5 Parameter