This parameter sets the voltage, which should correspond with the maximum value of the
selected function for the analog input 1 or 2. In the factory setting (setpoint) this value is
corresponds to the setpoint which is set via P105 >Maximum frequency<.
Note
SK 2x0E
For the adjustment of the analog inputs integrated in the SK2x0E to the type of analog signals,
the following values must be set:
0 - 10V
2 - 10V
0 - 20mA
4 - 20mA
DIP switches: (please see chapter 4.3.2.3 "DIP switches, analog input (only SK 2x0E)")
SK xU4-IOE
Standardization to typical signals such as 0(2)-10 V or 0(4)-20 mA is carried out via the DIP
switch on the I/O-extension module. In this case, additional adjustment of parameters (P402) and
(P403) must not be carried out.
Pos : 437 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P404 – Filter Anal ogei ngang [SK 1x 0E, SK 2xx E, SK 54x E, SK 2xxE-FD S] @ 0\m od_1327681301144_14638.docx @ 14975 @ @ 1
P404
Filter Analogeingang
[-01]
(Analog input filter)
[-02]
10 ... 400 ms
Adjustable digital low-pass filter for the analog signal. Interference peaks are hidden, the reaction
time is extended.
{ all 100 }
[-01] = analog input 1: analog input 1 integrated in the device
[-02] = analog input 2: analog input 2 integrated in the device
The filter time for the analog inputs of the optional external IO extension modules is set in the
parameter set for the relevant module (P161).
Pos : 438 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
BU 0200 en-US-4920
→ 10.00 V
→ 10.00 V
→ 5.00 V (enable internal resistance via DIP switch!)
→ 5.00 V (enable internal resistance via DIP switch!)