NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 467 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P465 – Festfr equenz Fel d [SK 1x0E, SK 2xx E, SK 2x xE-FD S] @ 2\mod_1346931809249_14638.docx @ 42860 @ @ 1
P465
[-01]
fixed frequency Array
...
(fixed frequency/frequency array)
[-15]
-400.0 ... 400.0 Hz
In the array levels, up to 15 different fixed frequencies can be set, which in turn can be encoded
for the functions 50...54 in binary code for the digital inputs.
{ [-01] = 5.0 }
{ [-02] = 10.0 }
{ [-03] = 20.0 }
[-01] = Fixed frequency 1/array 1
{ [-04] = 35.0 }
[-02] = Fixed frequency 2/array 2
{ [-05] = 50.0 }
[-03] = Fixed frequency 3/array 3
{ [-06] = 70.0 }
[-04] = Fixed frequency 4/array 4
{ [-07] = 100.0 }
[-05] = Fixed frequency array 5
{ [-08] = 0.0 }
[-06] = Fixed frequency array 6
{ [-09] = -5.0 }
[-07] = Fixed frequency array 7
{ [-10] = -10.0 }
[-08] = Fixed frequency array 8
{ [-11] = -20.0 }
{ [-12] = -35.0 }
{ [-13] = -50.0 }
{ [-14] = -70.0 }
{ [-15] = -100.0 }
Pos : 468 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P466 – Minim alfrequenz Proz essr egler @ 0\mod_1328002464186_14638.docx @ 15034 @ @ 1
P466
Min. freq. proc.ctrl.
(minimum frequency process controller)
0.0 ... 400.0 Hz
With the aid of the minimum frequency process controller the control ratio can also be kept to a
minimum ratio, even with a master value of "zero", in order to enable adjustment of the
{ 0.0 }
compensator. Further details in P400 and (chapter 8.2).
Pos : 469 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P475 – Ei n-/ Ausschaltv erz ögerung Digitalfunkti on [SK 2xx E] @ 2\m od_1346931809920_14638.docx @ 42884 @ @ 1
P475
[-01]
delay on/off switch
...
(digital function switch on/off delay)
[-04]
-30,000 ... 30,000 s
Adjustable switch-on/off delay for digital inputs and digital functions of the analog inputs. Use as a
switch-on filter or simple process control is possible.
{ 0,000 }
[-01] = Digital input 1
[-02] = Digital input 2
[-03] = Digital input 3
[-04] = Digital input 4
Pos : 470 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
184
[-09] = Fixed frequency array 9
[-10] = Fixed frequency array 10
[-11] = Fixed frequency array 11
[-12] = Fixed frequency array 12
[-13] = Fixed frequency array 13
[-14] = Fixed frequency array 14
[-15] = Fixed frequency array 15
Positive values = switch-on delayed
Negative values = switch-off delayed
BU 0200 en-US-4920