NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 527 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P533 – Faktor I2t-Motor @ 0\m od_1328093471572_14638.docx @ 15071 @ @ 1
Factor I
P533
(factor I
50 ... 150 %
The motor current for the I
Larger factors permit larger currents.
{ 100 }
Pos : 528 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P534 – Mom entenabschaltgrenz e @ 0\mod_1328093515135_14638.docx @ 15072 @ @ 1
P534
Torque disconnection limit
[-01]
(Torque disconnection limit)
[-02]
0 ... 400%/401
Via this parameter both the motoring [-01] and the regenerative [-02] switch-off value can be
adjusted.
{ all 401 }
If 80 % of the set value is reached, a warning status is set. At 100 % switch-off is performed with
an error message.
Error 12.1 is given on exceeding the drive switch-off limit and 12.2on exceeding the generator
switch-off limit.
401 = OFF,
Pos : 529 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P535 – I2t-Motor @ 58\mod_1606131402733_14638.doc x @ 2694888 @ @ 1
2
I
t motor
P535
(I
2
t motor)
0 ... 24
The motor temperature is calculated depending on the output current, the time and the output
frequency (cooling). If the temperature limit value is reached then switch off occurs and error
{ 0 }
message E002 (motor overheating) is output. Possible positive or negative acting ambient
conditions cannot be taken into account here.
The I
different triggering times (<5 s, <10 s and <20 s) can be set. The trigger times are based on
classes 5, 10 and 20 for semiconductor switching devices. The recommended setting for standard
applications is P535=5.
All curves run from 0 Hz to half of the nominal motor frequency (P201). The full nominal current is
available from half of the nominal frequency upwards.
With multi-motor operation the monitoring must be disabled.
I²t motor off Monitoring is inactive
Switch off class 5,
60 s at (1.5 x I
I
N
100%
90%
80%
70%
60%
50%
40%
30%
NOTE:
Pos : 530 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
198
2
t Motor
2
t motor)
2
t motor monitoring P535 can be weighted with the parameter P533.
[01] = motoring limit
means that this function has been disabled.
2
t motor function can be set in a differentiated manner. 8 characteristic curves with three
x P533)
N
at 0 Hz
P535
1
2
3
4
5
6
7
8
Shut-off classes 10 and 20 are provided for applications with heavy starting.
When using these shut-off classes, it must be ensured that the VFD has a
sufficiently high overload capacity.
Switch off class 10,
120 s at (1.5 x I
x P533)
N
I
at 0 Hz
P535
N
100%
9
90%
10
80%
11
70%
12
60%
13
50%
14
40%
15
30%
16
S
S
[02] = regenerative limit
Switch off class 20,
240 s at (1.5 x I
x P533)
N
I
at 0 Hz
P535
N
100%
17
90%
18
80%
19
70%
20
60%
21
50%
22
40%
23
30%
24
BU 0200 en-US-4920