NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
17 =
Comparison val. AIN2,
SK 2x0E:
Setpoint AIN2 of the VFD is compared with the value in (P435[-01 or -02]).
SK 2x5E: Setpoint AIN2 of 1st I/O extension is compared with value in
(P435[-01])
18 =
Inverter ready: The VFD is ready for operation. After being enabled it delivers
an output signal.
19 =
... 27 reserved
28 =
Rotor pos. PMSM ok
The PMSM rotor position is known.
29 =
Reserved
30 =
Status dig in 1
31 =
Status dig in 2
32 =
Status dig in 3
33 =
Status dig in 4
38 =
Value Bus Setpoint
39 =
STO inactive
40 =
Output via PLC: The output is set by the integrated PLC
Pos : 460 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P434 – Digitalausg ang_Inform ati on "l ow-aktive Ei nstellungen/F unktionen" [alle FU ] @ 19\m od_1505978722699_14638.docx @ 2365680 @ @ 1
If the variable frequency drive is not in operation, i.e. no line or control voltage is connected, all
outputs have no function ("low"). This means that the following must be taken into account
when using settings or functions that are "low" active (e.g setting 7  Fault):
Evaluation of the output signal of the device, e.g. by a PLC must be compared with the basic
readiness for operation of the variable frequency drive.
Pos : 461 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P435 – Normi erung Digitalausgänge [SK 1x 0E, SK 2xx E, SK 2xx E-FDS] @ 2\m od_1346931807892_14638.docx @ 42812 @ @ 1
P435
Dig. out scaling
[-01]
(digital output standardization)
[-02]
-400 ... 400 %
[-01] =
{ 100 }
[-02] =
Adjustment of the limits of the output function. For a negative value, the output function will be
output negative.
Reference to the following values:
Pos : 462 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
182
Information
Digital output 1, Digital output 1 of the variable frequency drive
Digital output 2, Digital output 2 of the variable frequency drive SK 2x0E
Current limit (3) = x [%] ⋅ P203 >Rated motor current<
Torque current limit (4) = x [%] ⋅ P203 ⋅ P206 (calculated rated motor torque)
Frequency limit (5) = x [%] ⋅ P201 >Rated motor frequency<
POSICON functions see BU 0210
"low" active settings/functions
BU 0200 en-US-4920
High
High
High
High
High
High
High
High
High
High