nord NORDAC FLEX SK 200E Series User Manual page 231

Table of Contents

Advertisement

Pos : 687 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/War nmel dungen (T abellenübersc hrift) @ 3\mod_1361803463080_14638.docx @ 59918 @ 5 @ 1
Warning messages
Display in the
Simple Box/Control Box Warning
Text in the Parameter Box
Group
Details in
P700 [-02]
Pos : 688 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/W arnung C 001 [SK 180E ... SK 5x xE/SK 300P/SK 500P] @ 2\mod_1347456220101_14638.docx @ 46976 @ @ 1
C001
1.0
Inverter overtemp.
"Inverter overtemperature"
(inverter heat sink)
Pos : 689 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/W arnung C 002 [SK 180E/SK 2xx E/SK 5x xE/SK2x xE-FD S/SK 500P] @ 2\m od_1347456223954_14638.docx @ 47001 @ @ 1
C002
2.0
Motor overtemp. PTC
"Motor overtemp. PTC"
2.1
Motor overtemp. I²t
"Motor overtemperature I²t"
Only if I
programmed.
2.2
Ext Resistor Temp
"Overtemperature of external
braking resistor"
Overtemperature via digital
input (P420 [...])={13}
Pos : 690 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/W arnung C 003 [SK 180E ... SK 5x xE] @ 2\m od_1347457006237_14638.docx @ 47200 @ @ 1
2
C003
3.0
I
3.1
Chopper overtemperature I
3.5
Torque current limit
3.6
Current limit
Pos : 691 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
BU 0200 en-US-4920
2
t motor (P535) is
t overcurrent limit
6 Operating status messages
Cause
Remedy
Temperature monitoring of the inverter
Warning, permissible temperature limit reached.
Reduce ambient temperature
Check device fan/cabinet ventilation
Check the device for dirt
Warning from motor temperature sensor (triggering
threshold reached)
Reduce motor load
Increase motor speed
Use external motor fan
Warning: I2t motor monitoring (1.3 times the rated current
reached for the time period specified in (P535))
Reduce motor load
Increase motor speed
Warning: Temperature monitor (e.g. braking resistor) has
activated
Digital input is low
Warning: a.c. inverter: I
for 60 s (also note P504)
Continuous overload at inverter output
2
2
t
Warning: I
t limit for the brake chopper has activated, 1.3
times values reached for 60 s (please also pay attention to
P554, if present, and P555, P556, P557)
Avoid overcurrent in brake resistance
Warning: Torque current limit reached
Check (P112)
Warning: Current limit reached
Check (P536)
2
t limit has triggered, e.g. > 1.3 x I
n
231

Advertisement

Table of Contents
loading

Table of Contents