Pos : 503 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P515 – CAN- Adr ess e_01 [SK 1x 0E, SK 2x xE, SK 2xx E-FDS] @ 2\mod_1346932167813_14638.docx @ 43172 @ @ 1
P515
[-01]
CAN bus address
...
(CAN address (system bus))
[-03]
0 ... 255
Setting of the systembus address.
dec
{ all 32
}
dec
[-01] = Slave address, Receive address for system bus
or { all 20
}
hex
[-02] = Broadcast slave address, system bus reception address (slave)
[-03] = Master address, "Broadcast master address", transmission address for system bus
(master)
NOTE: If up to four VFD are to be linked via the system bus, the addresses must be set as follows VFD 1
= 32, VFD 2 = 34, VFD 3 = 36, VFD 4 = 38.
Pos : 504 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P515 – CAN- Adr ess e_02 [SK 1x 0E, SK 2x xE] @ 17\m od_1490096962359_14638.docx @ 2336235 @ @ 1
The system bus addresses should be set via DIP switches (chapter 4.3.2.2).
Pos : 505 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P516 – Aus blendfrequenz 1 @ 0\mod_1328092606664_14638.docx @ 15057 @ @ 1
Skip frequency 1
P516
(skip frequency 1)
0.0 ... 400.0 Hz
The output frequency around the frequency value (P517) set here is not shown.
{ 0.0 }
This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.
0.0 = Skip frequency inactive
Pos : 506 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P517 – Aus blendbereic h 1 @ 0\mod_1328092662665_14638.doc x @ 15058 @ @ 1
Skip frequency area 1
P517
(skip frequency range 1)
0.0 ... 50.0 Hz
Skip range for the >Skip frequency 1< P516. This frequency value is added and subtracted from
the skip frequency.
{ 2.0 }
Skip frequency area 1: P516 - P517 ... P516 + P517
Pos : 507 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P518 – Aus blendfrequenz 2 @ 0\mod_1328092706493_14638.docx @ 15059 @ @ 1
Skip frequency 2
P518
(skip frequency 2)
0.0 ... 400.0 Hz
The output frequency around the frequency value (P519) set here is not shown.
{ 0.0 }
This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.
0.0 = Skip frequency inactive
Pos : 508 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P519 – Aus blendbereic h 2 @ 0\mod_1328092748353_14638.doc x @ 15060 @ @ 1
Skip frequency area 2
P519
(skip frequency range 2)
0.0 ... 50.0 Hz
Skip range for the >Skip frequency 2< P518. This frequency value is added and subtracted from
the skip frequency.
{ 2.0 }
Skip frequency area 2: P518 - P519 ... P518 + P519
Pos : 509 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
BU 0200 en-US-4920
5 Parameter
S
S
P
S
P
S
P
S
P
193