NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 341 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Param eter P203 – Motor N enns trom @ 41\mod_1586433053290_14638.doc x @ 2601030 @ @ 1
Nominal current
P203
(rated motor current)
0.1 ... 1000.0 A
The rated motor current is a decisive parameter for current vector control.
{ see information }
Default setting
The default setting depends on the rated VFD output or the setting in P200.
Pos : 342 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Param eter P204 – Motor N enns pannung @ 41\mod_1586433246488_14638.docx @ 2601066 @ @ 1
Nominal voltage
P204
(rated motor voltage)
100 ... 800 V
The rated motor voltage adjusts the line voltage to the motor voltage. In combination with the rated
{ see information }
frequency, the voltage/frequency characteristic curve is produced.
Default setting
The default setting depends on the rated VFD output or the setting in P200.
Pos : 343 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Param eter P205 – Motor N ennl eistung @ 41\mod_1586433362067_14638.docx @ 2601102 @ @ 1
Nominal power
P205
(Rated motor output)
0.00 ... 250.00 kW
The rated motor output controls the motor set via P200.
{ see information }
Default setting
The default setting depends on the rated VFD output or the setting in P200.
Pos : 344 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Param eter P206 – Motor c os phi @ 41\m od_1586434114694_14638.docx @ 2601138 @ @ 1
Cos phi
P206
(motor cos
0.50 ... 0.95
The motor cos ϕ is a decisive parameter for current vector control.
{ see information }
Default setting
The default setting depends on the rated VFD output or the setting in P200.
Pos : 345 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Param eter P206 – Motor c os phi_Info_PM SM @ 19\mod_1505894620817_14638.docx @ 2365515 @ @ 1
This parameter is not relevant if a PMSM is used.
Pos : 346 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Param eter P207 – Motorsc haltung @ 41\m od_1586434261620_14638.docx @ 2601174 @ @ 1
Star Delta con.
P207
(motor circuit )
0 ... 1
0 = star
{ see information }
The motor circuit is crucial for stator resistance measurement (P220) and therefore critical for
current vector control.
Default setting
The default setting depends on the rated VFD output or the setting in P200.
Pos : 347 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
Pos : 348 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Param eter P208 – Statorwiderstand @ 41\mod_1586435136682_14638.docx @ 2601210 @ @ 1