Input voltage
P728
(input voltage)
0 ... 1000 V
Displays the actual line voltage at the VFD input. This is determined indirectly from the value of
the DC link voltage.
Pos : 602 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Param eter P728 – Netzs pannung _ Statischer Betrag bei 24 V Geräten [SK 2xx E, SK 2x xE-FD S] @ 5\m od_1397203354385_14638.docx @ 126308 @ @ 1
In devices with a separate 24 V supply, a static value is displayed if no line voltage is present
(e.g.: with 1~ 230 V devices: P728 = 230 V). This value is used for internal initialization
purposes.
Pos : 603 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Param eter P729 – Drehmom ent @ 0\mod_1328173426559_14638.docx @ 15133 @ @ 1
Torque
P729
(Torque )
-400 ... 400 %
Displays the actual calculated torque. Basis for calculation are the motor data P201...P209.
Pos : 604 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Param eter P730 – Fel d @ 0\m od_1328173473274_14638.docx @ 15134 @ @ 1
Field
P730
(Field)
0 ... 100 %
Displays the actual field in the motor calculated by the VFD. Basis for calculation are the motor
data P201...P209.
Pos : 605 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Param eter P731 – Ak tueller Param etersatz @ 0\mod_1328173520271_14638.docx @ 15135 @ @ 1
Parameter set
P731
(current parameter set)
0 ... 3
Shows the actual operating parameter set.
Pos : 606 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Param eter P732 – Strom Phas e U @ 0\m od_1328173601208_14638.docx @ 15136 @ @ 1
Phase U current
P732
(U phase current)
0.0 ... 999.9 A
Displays the actual U phase current.
NOTE:
This value can deviate somewhat from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
Pos : 607 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Param eter P733 – Strom Phas e V @ 0\mod_1328173830046_14638.doc x @ 15137 @ @ 1
Phase V current
P733
(V phase current)
0.0 ... 999.9 A
Displays the actual V phase current.
NOTE:
This value can deviate somewhat from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
Pos : 608 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
Pos : 609 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Param eter P734 – Strom Phas e W @ 0\m od_1328173871579_14638.docx @ 15138 @ @ 1
Phase W current
P734
(W phase current)
0.0 ... 999.9 A
Displays the actual W phase current.
NOTE:
This value can deviate somewhat from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
Pos : 610 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Param eter P735 – Drehz ahl Dr ehg eber [SK 2xxE, SK 2xx E-FDS] @ 2\mod_1347348492128_14638.doc x @ 44460 @ @ 1
Speed encoder
P735
(encoder speed)
-9999 ... 9999 rpm
Displays the actual rotation speed supplied by the incremental encoder. For this, P301 must be
correctly set.
Pos : 611 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Param eter P736 – Zwisc henkreis spannung @ 0\m od_1328174969216_14638.docx @ 15141 @ @ 1
214
Information
0 = Parameter set 1
1 = Parameter set 2
Display of static value
2 = Parameter set 3
3 = Parameter set 4