nord NORDAC FLEX SK 200E Series User Manual page 229

Table of Contents

Advertisement

12.4
Current limit
12.5
Load monitor
12.8
AI minimum,
"Analog In minimum"
12.9
AI maximum,
"Analog In maximum"
Pos : 674 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
Pos : 675 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E013 [SK 200E ... SK 5xxE] @ 2\mod_1347454271218_14638.doc x @ 46752 @ @ 1
E013
13.0
Encoder error
13.1
Speed slip error
"Speed slip error"
13.2
Disconnect. control,
"Shut-down monitoring"
13.5
Reserved
13.6
Reserved
Pos : 676 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E014 "res erviert" [SK 200E ... SK 5xxE/SK 500P] @ 2\m od_1347454273854_14638.docx @ 46777 @ @ 1
E014
---
Reserved
Pos : 677 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E015 [SK 180E ... SK 5xxE] @ 2\mod_1347454278051_14638.doc x @ 46802 @ @ 1
E015
---
Reserved
Pos : 678 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E016 [SK 135E ... SK 5xxE, SK xxx E-FDS] @ 2\m od_1347454280625_14638.docx @ 46827 @ @ 1
E016
16.0
Motor phase error
16.1
Magn. Current Watch
"Magnetizing current
monitoring"
Pos : 679 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E018 "res erviert" [SK 2xx E/SK 5xxE/SK 2xx E-FDS, SK 500P] @ 44\m od_1594726433780_14638.docx @ 2645278 @ @ 1
E018
18.0
Reserved
Pos : 680 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E019 [SK 180E/SK 2x xE/SK 5xxE/SK2xxE-FD S, auß er SK 500P] @ 2\mod_1347454285788_14638.docx @ 46877 @ @ 1
E019
19.0
parameter ident.
"Parameter identification"
BU 0200 en-US-4920
6 Operating status messages
Limit from potentiometer or setpoint source has switched off.
P400 = 14
Switch-off due to overshooting or undershooting of
permissible load torques ((P525) ... (P529)) for the time set
in (P528).
Adjust load
Change limit values ((P525) ... (P527))
Increase delay time (P528)
Change monitoring mode (P529)
Switch-off due to undershooting of the 0% adjustment value
(P402) with setting (P401) "0-10 V with switch-off on error 1"
or "....2"
Switch-off due to overshooting of the 100% adjustment
value (P402) with setting (P401) "0-10 V with switch-off on
error 1" or "....2"
No signal from encoder
Check 5 V sensor if available
Check supply voltage of encoder
The slip speed error limit was reached.
• Increase value in P327
The slip error monitoring was triggered; the motor could not
follow the setpoint.
Check motor data P201-P209! (important for current
controllers)
Check motor circuit
Check encoder settings P300 and following in servo
mode
Increase value for torque limit in P112
Increase value for current limit in P536
Check deceleration time P103 and extend if
necessary
Error message for POSICON  see supplementary manual
Error message for POSICON  see supplementary manual
Error message for POSICON  see supplementary manual
A motor phase is not connected.
Check P539
Check motor connection
Required exciting current not achieved at moment of switch-
on.
Check P539
Check motor connection
Error message for "Safe Pulse Block", see supplementary
instructions
Automatic identification of the connected motor was
unsuccessful
229