NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 414 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P336 – Mode R otorl agenident. [SK 2xx E(-FDS), SK 5x xE] @ 38\m od_1568383147815_14638.docx @ 2559466 @ @ 1
Mode rotorpos. ident.
P336
(Rotor position identification mode)
0 ... 2
The exact position of the rotor must be known in order to operate a PMSM. This can be
determined by various methods.
{ 6 }
0 = First enable
1 = Supply voltage
2 = DIN/BUS IO IN
NOTE:
Identification of the rotor position is only performed if the VFD is in the "ready to switch-on" state
and the rotor position is not known (see P434, P481 function 28).
Use of the parameter is only advisable if the test signal method is set (P330).
Pos : 415 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P350 – PLC F unkti onalität @ 9\mod_1448362540297_14638.doc x @ 266317 @ @ 1
PLC functionality
P350
(PLC functionality)
0 ... 1
Activation of the integrated PLC
{ 0 }
0 = Off: the PLC is not active, the variable frequency drive is actuated in accordance with
1 = On: the PLC is active, variable frequency drive is actuated via the PLC depending on
Pos : 416 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P351 – PLC Sollw ert Auswahl @ 9\mod_1448363001241_14638.doc x @ 266380 @ @ 1
PLC Setvalue selection
P351
(PLC setpoint selection)
0 ... 3
Selection of the source for the control word (CTW) and the main setpoint (MSW) with active PLC
functionality (P350 = 1). With the settings "0" and "1", the main setpoints are defined via (P553),
{ 0 }
but the definition of the auxiliary setpoints remains unchanged via (P546). This parameter is only
accepted if the variable frequency drive is in "ready for switch-on" status.
0 = CTW &MSW = PLC: The PLC supplies the control word (CTW) and the main setpoint
1 = CTW= P509: The PLC supplies the main setpoint (MSW), the control word (CTW)
2 = MSW = P510[1]: The PLC supplies the control word (CTW), the source for the main
3 = CTW & MSW = P509/510: The source for the control word (CTW) and the main setpoint
Pos : 417 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
164
parameters (P509) and (P510).
(P351). The main setpoints must be defined accordingly in parameter (P553). Auxiliary
setpoints (P510[-02]) can still be defined via (P546).
(MSW), and parameters (P509) and (P510[-01]) have no function.
corresponds to the setting in parameter (P509).
setpoint (MSW) corresponds to the setting in parameter (P510[-01]).
(MSW) corresponds to the setting in parameter (P509)/(P510[-01]).
Identification of the PMSM rotor position is performed when the
drive is enabled for the first time.
Identification of the PMSM rotor position is performed when the
supply voltage is applied for the first time.
Identification of the PMSM rotor position is triggered by an
external order by means of a binary bit (digital input (P420) or
Bus-in bit (480), setting "79", "Rotorpos. Ident.").
S
S
S
BU 0200 en-US-4920