NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 692 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/W arnung C 004 [SK 180E ... SK 5x xE/SK 500P] @ 2\mod_1347457006705_14638.doc x @ 47225 @ @ 1
C004
4.1
Overcurrent measurem
"Overcurrent measurement"
Pos : 693 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/W arnung C 008 [SK 180E ... SK 5x xE/SK 500P] @ 2\mod_1347457201563_14638.doc x @ 47250 @ @ 1
C008
8.0
Parameter loss
Pos : 694 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/W arnung C 012 [SK 180E ... SK 2x xE] @ 2\m od_1347457201968_14638.docx @ 47275 @ @ 1
C012
12.1
Limit moto./Customer
"Motor switch-off limit"
12.2
Limit gen.
"Generator switch-off limit"
12.3
Torque limit
12.4
Current limit
12.5
Load monitor
Pos : 695 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
232
Warning: pulse switch off is active
The limit for activation of pulse switch off (P537) has been
reached (only possible if P112 and P536 are switched off)
VFD is overloaded
Drive sluggish, insufficiently sized,
Ramps (P102/P103) too steep -> Increase ramp time
Check motor data (P201 ... P209)
Switch off slip compensation (P212)
Warning: One of the cyclically saved messages such as
operating hours
enabling time
or
successfully.
The warning disappears as soon as saving can be
successfully performed.
Warning: 80% of the drive switch-off limit (P534 [-01]) has
been exceeded.
Reduce load on motor
Set higher value in (P534 -[01])
Warning: 80% of the generator switch-off limit (P534 [-02])
has been reached.
Reduce load on motor
Set higher value in (P534 [-02]).
Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 12
Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 14
Warning due to overshooting or undershooting of
permissible load torques ((P525) ... (P529)) for the time set
in (P528).
Adjust load
Change limit values ((P525) ... (P527))
Increase delay time (P528)
could not be saved
BU 0200 en-US-4920