NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 692 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/W arnung C 004 [SK 180E ... SK 5x xE/SK 500P] @ 2\mod_1347457006705_14638.doc x @ 47225 @ @ 1
C004
4.1
Overcurrent measurem
"Overcurrent measurement"
Pos : 693 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/W arnung C 008 [SK 180E ... SK 5x xE/SK 500P] @ 2\mod_1347457201563_14638.doc x @ 47250 @ @ 1
C008
8.0
Parameter loss
Pos : 694 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/W arnung C 012 [SK 180E ... SK 2x xE] @ 2\m od_1347457201968_14638.docx @ 47275 @ @ 1
C012
12.1
Limit moto./Customer
"Motor switch-off limit"
12.2
Limit gen.
"Generator switch-off limit"
12.3
Torque limit
12.4
Current limit
12.5
Load monitor
Pos : 695 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
232
Warning: pulse switch off is active
The limit for activation of pulse switch off (P537) has been
reached (only possible if P112 and P536 are switched off)
•
VFD is overloaded
•
Drive sluggish, insufficiently sized,
•
Ramps (P102/P103) too steep -> Increase ramp time
•
Check motor data (P201 ... P209)
•
Switch off slip compensation (P212)
Warning: One of the cyclically saved messages such as
operating hours
enabling time
or
successfully.
The warning disappears as soon as saving can be
successfully performed.
Warning: 80% of the drive switch-off limit (P534 [-01]) has
been exceeded.
•
Reduce load on motor
•
Set higher value in (P534 -[01])
Warning: 80% of the generator switch-off limit (P534 [-02])
has been reached.
•
Reduce load on motor
•
Set higher value in (P534 [-02]).
Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 12
Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 14
Warning due to overshooting or undershooting of
permissible load torques ((P525) ... (P529)) for the time set
in (P528).
•
Adjust load
•
Change limit values ((P525) ... (P527))
•
Increase delay time (P528)
could not be saved