Notifications switch-on block, "not ready"
Display in the
SimpleBox /
Reason:
ControlBox
Text in the ParameterBox
Group
Details in
P700 [-03]
Pos : 697 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/Information I000_01 [SK 180E ... SK 5x xE/SK 500P] @ 2\mod_1347457775195_14638.doc x @ 47348 @ @ 1
I000
0.1
Disable voltage from IO
0.2
IO fast stop
0.3
Block voltage from bus
0.4
Bus fast stop
0.5
Enable on start
0.6 – 0.7
Reserved
Pos : 698 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/Information I000_02-Erg änz ung 08 und 09 [SK 180E ... SK 5xx E/SK 500P] @ 10\mod_1455725649528_14638.docx @ 306333 @ @ 1
0.8
Right direction blocked
0.9
Left direction blocked
Pos : 699 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/Information I006 [SK 180E ... SK 5xxE, auß er SK 500P] @ 2\m od_1347457929759_14638.docx @ 47373 @ @ 1
1)
I006
6.0
Charging error
Pos : 700 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/Information I011 [SK 180E ... SK 5xxE/SK 500P] @ 2\mod_1347457936856_14638.docx @ 47398 @ @ 1
I011
11.0
Analog Stop
Pos : 701 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/Information I014 "res erviert" [SK 200E ... SK 5xxE/ SK 500P] @ 2\m od_1347457944329_14638.docx @ 47423 @ @ 1
1)
I014
14.4
Reserved
Pos : 702 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/Information I018 "res erviert" [SK 2xx E/ SK 5xxE/ SK 2xx E-FDS/SK 500P] @ 2\m od_1347457946544_14638.docx @ 47448 @ @ 1
1)
I018
18.0
Reserved
Pos : 703 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/Information - Kennzeic hnung "Nic ht ber eit" @ 20\mod_1513067472948_14638.docx @ 2375119 @ @ 1
Indication of operating mode (message) on the Parameter Box or virtual operating unit of the NORD CON-Software: "Not ready"
1)
Pos : 705 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/FAQ Betriebsstörungen @ 9\mod_1448963314277_14638.doc x @ 268441 @ 2 @ 1
BU 0200 en-US-4920
6 Operating status messages
Cause
•
Remedy
If the "disable voltage" function is parameterized, input
(P420/P480) is Low
•
"Set high" input
•
Check signal cable (broken cable)
If the function "fast stop" is parameterized, input
(P420/P480) is at low
•
"Set high" input
•
Check signal cable (broken cable)
•
Bus operation (P509): control word bit 1 is "low"
•
Bus operation (P509): control word bit 2 is "low"
Enable signal (control word, Dig I/O or Bus I/O) was already
applied during the initialization phase (after line power "ON",
or control voltage "ON"). Or electrical phase is lacking.
•
Only issue enable signal after completion of
initialization (i.e. when the VFD is ready)
•
Activation of "Automatic Start" (P428)
Information message for PLC see supplementary
instructions
Switch-on block with inverter shut-off activated by:
P540 or by "Enable right block" (P420 = 31, 73) or "Enable
left block" (P420 = 32, 74),
The variable frequency drive switches to "Ready for
switching on" status
Charging relay not energized, because:
•
Line/DC link voltage too low
•
Line voltage failure
•
Evacuation run active ((P420)/(P480))
If an analog input of the variable frequency drive or a
connected IO extension is configured to detect cable breaks
(2-10 V signal or 4-20 mA signal), the variable frequency
drive switches to the status "ready for switch-on" if the
analog signal undershoots the value 1 V or 2 mA
This also occurs if the relevant analog input is
parameterized to function "0" ("no function").
•
Check connection
Information message for POSICON see supplementary
manual
Information message for "Safe stop" function see
supplementary manual