Speed Controller P
P310
(speed controller P)
0 ... 3200 %
P component of the speed controller (proportional amplification).
{ 100 }
Amplification factor by which the speed difference between the setpoint and actual frequency is
multiplied. A value of 100% means that a speed difference of 10% produces a setpoint of 10%.
Values that are too high can cause the output speed to oscillate.
Pos : 384 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P311 – Drehz ahl R egler I @ 0\mod_1327591756013_14638.docx @ 14942 @ @ 1
Speed Controller I
P311
(speed controller I)
0 ... 800%/ms
I component of the speed controller (integration component).
{ 20 }
The integration component of the controller enables the complete elimination of any control
deviation. The value indicates how large the setpoint change is per ms. Values that are too small
cause the controller to slow down (reset time is too long).
Pos : 385 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P312 – Mom entens tromregler P @ 0\m od_1327591805216_14638.docx @ 14943 @ @ 1
Torque current controller P
P312
(torque current controller P)
0 ... 1000 %
Current controller for the torque current. The higher the current controller parameter, the more
precisely the current setpoint maintained. Excessively high values in P312 generally lead to high-
{ 400 }
frequency oscillations at low speeds. On the other hand, excessively high values in P313 mostly
produce low-frequency oscillations across the whole speed range.
If the value "zero" is entered in P312 and P313, then torque current control is switched off. In this
case, only the motor model derivative action is used.
Pos : 386 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P313 – Mom entens tromregler I @ 0\mod_1327591883202_14638.docx @ 14944 @ @ 1
Torque current controller I
P313
(torque current controller I)
0 ... 800%/ms
I component of the torque current controller. (See also P312 >Torque current controller P<)
{ 50 }
Pos : 387 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P314 – Gr enz e M .-stromr egl. @ 0\m od_1327591927202_14638.docx @ 14945 @ @ 1
Torque current controller limit
P314
(Torque current controller limit)
0 ... 400 V
Determines the maximum voltage span of the torque current controller. The higher the value, the
greater the maximum effect that can be exercised by the torque current controller. Excessive
{ 400 }
values in P314, in particular, can lead to instability during transition to the field weakening range
(see P320). The values for P314 and P317 should always be set roughly the same so that the
field and torque current controllers are balanced.
Pos : 388 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P315 – Fel dstr omregler P @ 1\m od_1328618593561_14638.docx @ 15411 @ @ 1
Field current controller P
P315
(field current controller P)
0 ... 1000 %
Current controller for the field current. The higher the current controller parameters, the more
precisely the current setpoint maintained. Excessively high values for P315 generally lead to high-
{ 400 }
frequency vibrations at low speeds. On the other hand, excessively high values in P316 mostly
produce low-frequency vibrations across the whole speed range. If the value "zero" is entered in
P315 and P316, then the field current controller is switched off. In this case, only the motor model
derivative action is used.
Pos : 390 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Param eter P316 – Fel dstr omregler I @ 0\mod_1327592705182_14638.doc x @ 14947 @ @ 1
Field current controller I
P316
(field current controller I)
0 ... 800%/ms
I component of the field current controller. See also P315 >Field current controller P<
{ 50 }