NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 263 /Anleitungen/El ektr onik /FU und Starter/4. Inbetriebnahm e/SK 1x xE, SK 2xx E, -FD S/T emper aturs ensor en/KTY84- 130 Anschl uss _Ansc hl uss beis piel e_01_Option [SK 1x0E, SK 2xx E] @ 8\m od_1441635716619_14638.docx @ 240755 @ 5 @ 1
Connection examples
SK CU4-IOE / SK TU4-IOE-...
Connection of a KTY-84 to either of the two analog inputs of the relevant option is possible. In the
following examples, analog input 2 of the particular optional module is used.
SK CU4-IOE
Parameter settings (analog input 2)
The following parameters must be set for the function of the KTY84-130.
1.
Motor data P201-P207 must be set according to the nameplate.
2.
Motor stator resistance P208 is determined at 20°C with P220 = 1.
3.
Analog input 2 function, P400 [-04] = 30
(motor temperature)
4.
Analog input 2 mode, P401 [-02] = 1
(negative temperatures are also measured)
(from firmware version: V1.2)
5.
Adjustment of analog input 2: P402 [-02] = 1.54 V and P403 [-02] = 2.64 V
= 2.7 kΩ)
(with R
V
6.
Adjust time constants: P161 [-02] = 400 ms (filter time constant is at a maximum)
Parameter (P161) is a module parameter. It cannot be set on the variable frequency drive but directly on the I/O- module.
Communication takes place by directly connecting a Parameter Box to the RS232 interface of the module, for example, or by connecting
to the variable frequency drive via the system bus. (Parameter (P1101) object selection → ... )
7.
Motor temperature control (display): P739 [-03]