Value
Function
3
With SK 2x5 devices the variable frequency drive control unit must be supplied with power for a further 5 minutes after the last
change to the motor potentiometer in order to permanently save the data.
4
Function cannot be selected via BUS IO In Bits
5
The operating parameter set is selected via appropriately
parameterized digital inputs or BUS actuation. Switching can
take place during operation (online). Binary coding takes place
in accordance with the adjacent sample.
When enabled via the keyboard (Simple Box, Control Unit,
Potentiometer Unit or Parameter Box), the operating
parameter set will match the setting in P100.
Pos : 454 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
BU 0200 en-US-4920
Description
Setting
0 =
1 =
2 =
3 =
5 Parameter
Digital input
function [8]
Parameter set 1
LOW
Parameter set 2
HIGH
Parameter set 3
LOW
Parameter set 4
HIGH
Signal
Digital input
function [17]
LOW
LOW
HIGH
HIGH