Factory setting
P523
(factory setting)
0 ... 3
By selecting the appropriate value and confirming it with the Enter key, the selected parameter
range is entered in the factory setting. Once the setting has been made, the value of the
{ 0 }
parameter automatically returns to 0.
Pos : 516 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P523 – Werks einstellung_Ergänz ung Einstellung 3 [SK 2xx E, SK 250E-FD S] @ 59\mod_1606917961246_14638.doc x @ 2703020 @ @ 1
Pos : 517 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P523 – Werks einstellung_Ergänz ung [SK 2xx E] @ 9\m od_1448294698250_14638.docx @ 266034 @ @ 1
Note: If an external EEPROM ("memory module") is plugged in, then a value of ("Factory setting
...") only affect this. If no "memory module" is present, the set command ("Factory setting ...") is
applied to the internal EEPROM
Pos : 518 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P525 – Lastüberw ac hung Maximalwer t @ 0\mod_1328093087228_14638.docx @ 15065 @ @ 1
P525
[-01]
Load control max.
...
(load monitoring, maximum value)
[-03]
1 ... 400%/401
Selection of up to 3 auxiliary values:
{ all 401 }
[-01] = Auxiliary value 1
Maximum load torque value.
Setting of the upper limit of load monitoring. Up to 3 values can be specified. Prefixes are not
taken into account, only the integer values are processed (motor/generator torque, right/left
rotation). The array elements [-01], [-02] and [-03] of parameters (P525) ... (P527), or the entries
which are made there always belong together.
401 = OFF Means that the function is switched off. No monitoring is performed. This is also the
basic setting for the VFD.
Pos : 519 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Param eter P526 – Lastüberw ac hung Minim alwert @ 0\m od_1328093137197_14638.docx @ 15066 @ @ 1
P526
[-01]
Load control min.
...
(load monitoring, minimum value)
[-03]
0 ... 400 %
Selection of up to 3 auxiliary values:
{ all 0 }
[-01] = Auxiliary value 1
Minimum load torque.
Setting of the lower limit of load monitoring. Up to 3 values can be specified. Prefixes are not
taken into account, only the integer values are processed (motor/generator torque, right/left
rotation). The array elements [-01], [-02] and [-03] of parameters (P525) ... (P527), or the entries
which are made there always belong together.
0 = OFF
basic setting for the VFD.
Pos : 520 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
BU 0200 en-US-4920
0 = No change: Does not change the parameterization.
1 = Load factory setting: The complete parameterization of the VFD reverts to the factory
setting. All originally parameterized data are lost.
2 = Fact.setng.w.out bus All parameters of the variable frequency drive, but not the bus
parameters, are reset to the factory setting.
3 = Fact set w/o motor All parameters of the variable frequency drive, but not the motor
data parameters (P201 ... P209, P240 ... P246), are reset to the factory setting.
Up to firmware version V 2.2 R0 also the PMSM-relevant parameters (P240 to P246)
have been reset. This does no longer apply to the current firmware. The parameter
settings of these parameters now also remain unchanged.
Means that the function is switched off. No monitoring is performed. This is also the
[-02] = Auxiliary value 2
[-02] = Auxiliary value 2
5 Parameter
S
P
[-03] = Auxiliary value 3
S
P
[-03] = Auxiliary value 3