Nom.val process ctrl
P412
(setpoint process controller)
-10.0 ... 10.0 V
Fixed specification of a setpoint for the process controller that will only occasionally be altered.
{ 5.0 }
Only with P400 = 14 ... 16 (process control) 8.2 "Process controller".
Pos : 444 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P413 – P- Anteil PI-Regl er [SK 1x 0E, SK 2xx E, SK 2xx E-FDS] @ 2\m od_1346931799733_14638.docx @ 42523 @ @ 1
Pl -control P comp.
P413
(P component of PI controller)
0.0 ... 400.0 %
This parameter is only effective when the function PI controller actual frequency is selected.
{ 10.0 }
The P component of the PI controller determines the frequency jump if there is a control deviation
based on the control difference.
E.g.: At a setting of P413 = 10% and a rule difference of 50%, 5% is added to the actual setpoint.
Pos : 445 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P414 – I-Anteil PI-Regler [SK 1x 0E, SK 2xx E, SK 2xxE-FD S] @ 2\m od_1346931800404_14638.docx @ 42547 @ @ 1
PI control I comp.
P414
(I component of PI controller)
0.0 ... 3000.0 %/s
This parameter is only effective when the function PI controller actual frequency is selected.
{ 10.0 }
The I component of the PI controller determines the frequency change, dependent on time.
Note:
(Reason: better setting ability with small I-proportions).
Pos : 446 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P415 – Gr enz e Proz eßr egler [SK 1x 0E, SK 2x xE, SK 2xx E-FDS] @ 2\mod_1346931801199_14638.docx @ 42571 @ @ 1
Process control limit
P415
(Process controller control limit)
0 ... 400.0 %
This parameter is only effective when the function PI process control is selected. This
determines the control limit (%) after the PI controller (please see chapter 8.2 "Process
{ 10.0 }
controller").
Pos : 447 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P416 – Ram penz eit PI- Sollw ert [SK 1x0E, SK 2xxE, SK 2xx E-FDS] @ 2\mod_1346931801870_14638.doc x @ 42595 @ @ 1
Ramp time PI setpoint
P416
(ramp time PI setpoint)
0.00 ... 99.99 s
This parameter is only effective when the function PI process controller is selected.
{ 2.00 }
Ramp for PI setpoint
Pos : 448 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P417 – Offs et Anal ogausgang [SK 1x 0E, SK 2xx E, SK 2xxE-FD S] @ 2\m od_1346931802525_14638.docx @ 42619 @ @ 1
P417
[-01]
Offset analog output
...
(offset analog output)
[-02]
-10.0 ... 10.0 V
[-01] = IOE-1, AOUT of the first I/O extension (SK xU4-IOE)
{ all 0.0 }
[-02] = IOE-2, AOUT of the second I/O extension (SK xU4-IOE)
... only with
In the analog output function an offset can be entered to simplify the processing of the analog
SK CU4-IOE or SK
signal in other equipment.
TU4-IOE
If the analog output has been programmed with a digital function, then the difference between the
switch-on point and the switch-off point can be set in this parameter (hysteresis).
Pos : 449 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
BU 0200 en-US-4920
In contrast to other NORD series, parameter P414 is smaller by a factor of 100