nord NORDAC FLEX SK 200E Series User Manual page 180

Table of Contents

Advertisement

NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 455 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P426 – Sc hnell haltez eit [SK 1x 0E, SK 2xx E, SK 2xxE-FD S] @ 2\m od_1347348745067_14638.docx @ 44484 @ @ 1
Quick stop time
P426
(quick stop time)
0 ... 320.00 s
Setting of the stop time for the fast stop function which can be triggered either via a digital input,
the bus control, the keyboard or automatically in case of a fault.
{ 0.10 }
Emergency stop time is the time for the linear frequency decrease from the set maximum
frequency (P105) to 0 Hz. If an actual setpoint <100% is being used, the emergency stop time is
reduced correspondingly.
Pos : 456 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P427 – Sc hnell halt bei Störung [SK 2xx E, SK 2xx E-FDS] @ 2\m od_1346931805833_14638.docx @ 42740 @ @ 1
Quick stop on Error
P427
(Quick stop on error)
0 ... 2
Activation of automatic emergency stop following error
{ 0 }
A quick stop can be triggered by error E2.x, E7.0, E10.x, E12.8, E12.9 and E19.0.
Pos : 457 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Param eter P428 – Automatisc her Anl auf [SK 1x0E, SK 2xx E, SK 2x xE-FD S] @ 2\m od_1346931806519_14638.docx @ 42764 @ @ 1
Automatic starting
P428
(automatic start)
In the standard setting (P428 =0  Off) the VFD requires a flank to enable (signal change from
0 ... 1
"low high") at the relevant digital input.
{ 0 }
In the setting On  1 the VFD reacts to a high level. This function is only possible if the VFD is
controlled using the digital inputs. (see P509=0/1)
In some cases, the VFD must start up directly when line power is switched on. For this P428 = 1
 On can be set. If the enable signal is permanently switched on, or equipped with a cable
jumper, the VFD starts up immediately.
NOTE:
NOTE:
NOTE:
Pos : 458 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
180
0 = Switched off: Automatic emergency stop following error is deactivated
1 = reserved
2 = Switched on: Automatic emergency stop following fault
(P428) not "ON" if (P506) = 6, Danger! (See note on (P506))
The "Automatic Start" function can only be used if a digital input of the variable
frequency drive (DIN 1 ... DIN 4) is parameterized to the function "Enable Right" or
"Enable Left" and this input is permanently set to "high". The digital inputs of the
technology modules (e.g.:
function!
The "Automatic Start" function can only be activated if the variable frequency drive
has been parameterized to local control ((P509) setting { 0 } or { 1} ).
SK CU4 - IOE) do not support this "Automatic Start"
S
P
S
S
P
BU 0200 en-US-4920

Advertisement

Table of Contents
loading

Table of Contents