Configuring Outlet Current Thresholds
1. Click the Outlet Current Thresholds link at the bottom of the Outlets page:
2. The configuration page displays:
To set outlet current thresholds:
1. Provide threshold hysteresis between event state and recovery (A). the range is 0.0-10.0A; the default is
1.0A.
2. Set the low/high alarm and low/high warning threshold values (A) for outlet current load. The range is min
0.0A; max is max current shown in the show outlets command.
3. Click Apply.
PRO1 Sentry Switched DC PDU
81 of 211